Description of Indicator:  

 

POWER (Green) power indicator: 

If the controller is charged, this indicator lights up to indicate that controller is under normal operation.  
 

TORQUE (Red) over-current indicator

T

urns red to indicate that output current of the controller exceeds client’s 

pre-set current, and the controller will automatically 

limit the output current to such value. 
 

Regulation Description of Functional Potentiometer

 

MAX (Maximum Revolving Speed Limit) 

It is used for limiting motor’s maximum revolving speed. Increase in clockwise rotation and decrease in 

counter clockwise rotation. 

 

IR (Torque Compensation) 

Regulate “IR” enable motor work under different loads and keep re

volving speed constant (normally factory default is 0), Increase 

in clockwise rotation and decrease in counter clockwise rotation. 
 

RAMP (Soft Start/ Stop) 

Regulate “RAMP” to set motor’s starting and stopping time (1

-20 S). Increase in clockwise rotation. 

 

TORQUE (Current Limit Regulation) 

Regulate “TORQUE” to set over

-current protection value of the controller; regulating range is 0-20A, Increase in clockwise rotation 

and decrease in counter clockwise rotation. When reaches over-current limit value, over-current indicator (Red) lights constantly 
and current is be limited to such value, at this time, continue to regulate the external potentiometer, current value is invariant( 
i.e. amplitude limiting). 
 

Driver Examination steps before Charged: 

 

 

Firstly, check  whether positive and negative connection of battery pack and driver is correct,  reliable and whether input 

power is within driver’s applicable range.

 

 

Check whether the circuit board of driver is clean, clear and without conductive metals, humidity, dew and debris 

 

Check whether periphery connecting line of driver is correct and free from short circuit and ground connection. 

 

Confirm that external speed governing potentiometer is at minimum position (given signal is at 0) 

 

Common Fault Treatment: 

PROBLEMS 

CAUSES 

RECOMMENDED SOLUTIONS 

Motor is out-of-
operation 

1. Wiring is incorrect. 
2. Command signal is

V.  

3. Disconnection of INHIBIT enable 
terminal. 
4. Current output is limited. 

1. Carefully check the wiring between controller and motor 
2. Regulate external potentiometer or external analogue signal 
3. Contact enable terminal 
4. Regulate the output current of controller after confirming that 
motor is not blocked 

Acceleration and 
deceleration time of 
motor is improper 

Regulate of starting and breaking 
potentiometer is inappropriate 

Regulate starting and breaking potentiometer 

Motor vibrates after 
acting load 

1. IR COMP setting is too big 
2. Lack of current limit 

1. Carefully regulate the setting of IR COMP  
2. Regulate the TORQUE potentiometer after confirming that motor 
matches well with the driver 

Speed up after acting 
load of motor 

IR COMP setting is too small 

Increase IR COMP setting 

Slow down after 
acting load of motor 

IR COMP setting is too big 

Decrease IR COMP setting 

 