background image

Configuration fall-delay time 

6.3

Display

Fall-delay time

001

none

002

100 ms

003

*

200 ms

004

500 ms

005

1000 ms

Most important technical data

8

Press the «Mode» button briefly.
Use the «Data» button to set the required

fall-delay time

(according to Table 2).

Then briefly press the «Mode» button and End appears.

➔ 

The system is configured.

➔ 

Press «Data» button to restart.

Configuration mode (for configuration before starting up, 

via diagnostic menu, after mode «h»)

6

Please read chapters 6.1 to 6.3 in full before attempting configuration.

Configuration of safety edge inputs

6.2

Table 2

Display

E001

E002

E003

E004

E005

E006

E007

E101/ E102

Error

Safety edge (SE) 
malfunction

SE mal-
function

SE mal-
function

SE mal-
function

Cable circuit
malfunction

Mounting

config.

mode

Outputs not OK

Undervoltage/
overvoltage

Remedy

Check 
safety edge

Check 
SE 

Check 
SE 

Check 
SE 

Check cable 
circuit < 3 ohm

Check 
configuration

Check connection 
for outputs

Check supply

1

2

Error displays

7

If an error is detected then the outputs are deactivated and symbols 

 

and an error code are displayed. The status LED lights up red.

Should other fault messages appear, please contact your supplier.

Configuration menu

can be 

exited

at any time by pressing the

«Mode» button (2 s).
«End» is displayed 

Press «Data» button and release 

Restart undertaken with new configuration.

Error messages may occur when restarting
after configuration if the inputs do not match
the configuration.

Activating configuration menu 

6.1

Status LED flashes orange, 
press «Data» button

Press the «Mode» and «Data» buttons
simultaneously for 2 s.
Configuration menu is activated.

Use the «Data» button to set the 

configuration

you want for the safety edge inputs 
(according to Table 1).

The current setting for the safety edge
inputs is displayed.

Display

Mobile 
safety 
edge

CLOSE 

Mobile 
safety 
edge

OPEN 

Stationary 
safety 
edge

CLOSE  

Stationary 
safety 
edge

OPEN 

not configured

001*

X

X

X

002

X

X

X

X

003

X

X

004

X

X

005

X

006

X

X

X

007

X

X

X

008

X

X

009

X

X

010

X

011

X

UNC

*)

 F

ac

to

ry

 s

et

ti

ng

Table 1

*)

 F

ac

to

ry

 s

et

ti

ng

Operating voltage

InTra6 3

24 V AC/DC ± 15%, 

InTra6 3.LVAC

100-240 V AC
50/60 Hz

Power consumption

max. 3 VA

Safety edges

8,2 kOhm

Outputs

Semiconductor relay, 24 V DC, max. 50 mA    

Dimensions
(W x H x D)

Switching device 

 

22,5x94x88 mm

Coil 

:

50x25x22 mm 

Converter 

:

40x25x22 mm

Electrical installation

9.1

Mechanical mounting

9.2

Mounting

9

1. Check that electrical components are all present by referring to component list 9.3.
2. Mount switching device in designated position.
3. Mounting of mechanical parts (see chapters 9.2 and 9.3).
4. Connect electrical lines as shown in terminal diagram in chapter 2.

1. Check that mechanical components are all present by referring to component list 9.3
2. Mount the two mounting brackets 

and the coil 

.

3. Pull in the steel cable (see chapter 9.4 and 9.5). Mount converter INTR-MOB 

or 

  

4. Tension the steel cable 

 

cable and fix it via the retaining screw 

 

. The steel cable

 

must be able to move unimpeded

through the INTR-FIX60 coil

along the full length of the gate.

5. Connect steel cable 

 

as described in chapter 9.5. Make sure the connection with the gate offers low resistance

(clean the contact points and remove any paint).

6. Establish the electrical connection as shown in the terminal diagram in chapter 2.