• Air Velocity: 400-500 fpm [2-2.5m/s] maximum
• Air Temperature: 40°F – 110°F maximum [4°C – 43°C]
• Lamp Distance from Coil: 6in – 48in [152mm – 1219mm]
• Electrical Wiring: compliant with local and national code, UL/ETL standards
• Safety Measures: alarms and disconnects, warning signage, employee training
• Lamp Disposal: in accordance with local and national regulations (see lamprecycle.org
for more information)
• Insulation Guidelines for Safety: the use of UV resistant materials such as aluminum
reflectors, shielding, jacketing, and tape, may be indicated to protect non-UV-compatible
materials in the treatment area. Contact BioZone Scientific if specific questions arise
concerning material compatibility.
4
Recommendations for Effective CoilCare Installations
EMT/Conduit
In most situations, when the system is mounted to surfaces perpendicular to the
surface to be irradiated, L-brackets are attached to the wall or support with self-
tapping screws.
Measure the distance between the L-brackets and cut tubing 1” less than the distance
between L-brackets. Extend the tubing between the L-brackets and fasten at each
end.
1.
Install Framing
INSTALLATION INSTRUCTIONS
First, determine the ideal mounting location within the HVAC system, and then
configure the CoilCare system accordingly. CoilCare can be mounted to the air handler
wall or similar support several ways depending on the size, orientation, and distance
between the mounting surfaces and surfaces to be irradiated.
Contact your BioZone commercial UV specialist with any questions or concerns prior
to installation.