CoilCare Configuration Guidelines

• 

Maximum  germicidal  effectiveness  is  within  an  18in  [457mm]  radius  from  lamp 
center axis

• 

The optimal distance between lamp(s) and the irradiated surface is 12in [305mm]

• 

The distance between stacked lamps should not exceed 35in [889mm]

• 

The distance between end to end lamps should not exceed 12in [305mm]

• 

The distance of lamp ends to the edge of irradiated surface should not exceed 6in 
[152mm]

• 

Minimal germicidal effectiveness expected at/beyond 48in [1219mm] radius from 
lamp center axis

• 

When coil depth is more than 12in [305mm], treating both sides of the coil may be 
indicated

12” [ 305 mm] max. space between lamps

6” [152 mm] max. space to end of coils

Overlap lamps where necessary

SYSTEM CONFIGURATION GUIDELINES

3

Determine the dimensions of the evaporator 
coils or area to be treated.

1.

Use  the  guidelines  below  to  select  the 
proper configuration and number of lamps 
needed to treat the required dimensions.

2.

BioZone  Scientific  offers  free 
of  charge  UVCalc™  to  assist 
with  system  configuration  and 
selection.  Contact your BioZone 
commercial  UV  specialist  for 
more information. 

Содержание CoilCare Series

Страница 1: ...COILCARE X 2017 BioZone Scientific International Inc 81200012B Installation Instructions and Operating Manual CoilCare Series...

Страница 2: ...g efficiently The system is equipped with a UV lamp and a reflector to direct and focus UV light on the coil surface The water resistant power supply is easy to mount and can withstand the humid envir...

Страница 3: ...veness expected at beyond 48in 1219mm radius from lamp center axis When coil depth is more than 12in 305mm treating both sides of the coil may be indicated 12 305 mm max space between lamps 6 152 mm m...

Страница 4: ...tibility 4 Recommendations for Effective CoilCare Installations EMT Conduit In most situations when the system is mounted to surfaces perpendicular to the surface to be irradiated L brackets are attac...

Страница 5: ...t Use pipe coupling to extend the vertical support between the floor and ceiling for a snug fit Channel Strut In situations where larger coil surfaces require CoilCare systems comprising several UV la...

Страница 6: ...of the HVAC system that is convenient for access to the electrical supply and for connection to the UV lamps The power supply is weather resistant and is suitable for mounting to the interior or exter...

Страница 7: ...r handler and exterior for connections as needed INSTALLATION INSTRUCTIONS 7 1 Connect Lamps and Cables Arrangecablesasneededforinstallation Ifnecessary use the Optional 3 4 or 1 cable strain relief t...

Страница 8: ...g Label The UV Warning Label contains fields convenient to record installation and service information It is recommended to record installation and service details on the UV Warning Label as those fun...

Страница 9: ...DISCONNECT BEFORE SERVICING OPERATION AND MAINTENANCE 9 As needed periodically wipe the UV lamps with a clean cloth or alcohol swab to remove any accumulated dust or dirt This process should be perfor...

Страница 10: ...ow after they have exceeded their rated lifespan however their germ killing effectiveness diminishes with time so they must be replaced on schedule for the system to function properly Contactyourlocal...

Страница 11: ...tional Inc are used with this equip ment Consequential and incidental damages are not recoverable under this warranty Manufacturer assumes no liability for any harm which may occur as a result of the...

Страница 12: ...low 80 F 27 C UV output can decrease by as much as 50 Cooling effects are noted and are factored into CoilCare system design Reflectance Ultraviolet light can be reflected off of surfaces the degree o...

Отзывы: