CoilCare Configuration Guidelines
•
Maximum germicidal effectiveness is within an 18in [457mm] radius from lamp
center axis
•
The optimal distance between lamp(s) and the irradiated surface is 12in [305mm]
•
The distance between stacked lamps should not exceed 35in [889mm]
•
The distance between end to end lamps should not exceed 12in [305mm]
•
The distance of lamp ends to the edge of irradiated surface should not exceed 6in
[152mm]
•
Minimal germicidal effectiveness expected at/beyond 48in [1219mm] radius from
lamp center axis
•
When coil depth is more than 12in [305mm], treating both sides of the coil may be
indicated
12” [ 305 mm] max. space between lamps
6” [152 mm] max. space to end of coils
Overlap lamps where necessary
SYSTEM CONFIGURATION GUIDELINES
3
Determine the dimensions of the evaporator
coils or area to be treated.
1.
Use the guidelines below to select the
proper configuration and number of lamps
needed to treat the required dimensions.
2.
BioZone Scientific offers free
of charge UVCalc™ to assist
with system configuration and
selection. Contact your BioZone
commercial UV specialist for
more information.