WR-30 Point-to-Point Wireless Bridge Instruction Manual
28
Symptom
Possible Cause
Corrective Action
Destination device reads out of
range, zero, or incorrect.
Wireless device
has mismatched
input type.
• Make sure that input type on the device is
correct for the analog input being used.
Options are 4-20 mA, 0-10 V, 0-5 V, or 1-5
V.
Destination
device is not
scaled properly.
• Destination device must accept 4-20 mA
signal and be scaled to properly display the
signal. Check the manufacturer’s instruction
manual for how to do this.
Signal
connections are
improperly wired.
• Double check to make sure all of the signal
connections are properly wired to all
devices. Check wiring diagrams starting on
page 9.
Digital inputs are not
corresponding with digital
outputs.
Devices have
mismatched
input/output
settings.
• Check to make sure the digital connection is
programmed appropriately as either an input
or an output.
Devices are
improperly wired.
• Check to make sure all digital inputs and
outputs are properly wired to all devices.
Check wiring diagrams starting on page 9.
Device will not power on.
Not enough
voltage is coming
from the power
supply.
• Devices require at least 12 VDC each in
order to power on. Check that the power
supply is providing enough voltage to the
device and that there are not too many
devices drawing power from the supply.
Devices are
improperly wired.
• Check to make sure all power connections
are properly wired to all devices. Check
wiring diagrams starting on page 9.