8 Diagnosis, asset management and service

NCR-21    4 … 20 mA

54408-01-190131

PC with PACTware/DTM 

Control system with EDD 

8.3  Asset Management function

The instrument features self-monitoring and 

diagnostics according to NE 107 and VDI/

VDE 2650. In addition to the status messages 

in the following tables there are more detailed 

error messages available under the menu item 

"

Diagnostics

" via app or PACTware/DTM.

Status messages

The status messages are divided into the 

following categories:

Failure

Function check

Out of specification

Maintenance requirement

and explained by pictographs:

4

1

2

3

Abb. 31: Pictographs of the status messages
1  Failure - red

2  Out of specification - yellow

3  Function check - orange

4  Maintenance - blue

Failure:

 Due to a malfunction in the instrument, 

a fault message is output.

Function check:

 The instrument is being 

worked on, the measured value is temporarily 

invalid (for example during simulation).

Out of specification:

 The measured value is 

unreliable because an instrument specification 

was exceeded (e.g. electronics temperature).

Maintenance:

 Due to external influences, the 

instrument function is limited. The measurement 

is affected, but the measured value is still valid. 

Plan in maintenance for the instrument because 

a failure is expected in the near future (e.g. due 

to buildup).

Information:

The status messages are always active. 

It cannot be deactivated by the user.

Failure

Code
Text mes-

sage

Cause

Rectification

F013
no measured 

value availa-

ble

• 

Sensor does not 

detect an echo 

during operation

• 

Antenna system 

dirty or defective

• 

Check or correct 

installation and/

or parameter 

settings

• 

Clean or 

exchange pro-

cess component 

or antenna

F017
Adjustment 

span too 

small

• 

Adjustment not 

within specifi-

cation

• 

Change adjust-

ment according 

to the limit 

values (diffe-

rence between 

min. and max. 

≥ 10 mm)

F025
Error in the li-

nearization 

table

• 

Index markers 

are not conti-

nuously rising, 

for example 

illogical value 

pairs

• 

Check linearisa-

tion table

• 

Delete table/

Create new

F040
Error in the 

electronics

• 

Hardware defect

• 

Exchanging the 

electronics

• 

Send instrument 

for repair

F080

• 

General soft-

ware error

• 

Disconnect ope-

rating voltage 

briefly

F105
Determine 

measured 

value

• 

The instrument 

is still in the 

start phase, the 

measured value 

could not yet be 

determined

• 

Wait for the end 

of the switch-on 

phase

• 

Duration up to 

approx. 3 minu-

tes depending 

on the version 

and parameter 

settings

F113
Communica-

tion error

• 

EMC interfe-

rence

• 

Remove EMC 

influences

F125
Impermissib-

le electronics 

temperature

• 

Temperature of 

the electronics 

in the non-

specified range

• 

Check ambient 

temperature

925-0374 

Содержание NCR-21

Страница 1: ...Document ID 54408 EN Operating instructions NCR 21 Document ID 54408 925 0374...

Страница 2: ...wer supply 29 5 1 Preparing the connection 29 5 2 Wiring plan 29 6 Set up Bluetooth connection with smartphone tablet 30 6 1 Preparations 30 6 2 Connecting 30 6 3 Sensor parameter adjustment 30 7 Set...

Страница 3: ...ant operator During work on and with the device the requi red personal protective equipment must always be worn 2 2 Appropriate use NCR 21 is a sensor for continuous level measurement You can find det...

Страница 4: ...personnel The instrument must be stationary moun ted and the antenna directed vertically downward The mounting location must be at least 4 km away from radio astronomy stations unless special permiss...

Страница 5: ...ns This device shall be installed only at fixed locations The LPR device shall not operate while being moved or while inside a moving container Hand held applications are prohibited Marketing to resid...

Страница 6: ...rt and storage Chapter Disposal 3 Product description 3 1 Configuration Scope of delivery The scope of delivery encompasses Radar sensor with integrated Bluetooth module Documentation This operating i...

Страница 7: ...Functional principle The antenna of the radar sensor emits short radar pulses with a duration of approx 1 ns These pulses are reflected by the product and received by the antenna as echoes The transit...

Страница 8: ...process conditions Make sure before mounting that all parts of the instrument exposed to the process are suitable for the existing process conditions These are mainly Active measuring component Proce...

Страница 9: ...ge supply Power supply and current signal are carried on the same two wire cable The operating voltage can differ depending on the instrument version The data for power supply are specified in chap te...

Страница 10: ...h your iPad Press Pair Android The coupling passes through automatically Enter PIN For authentication enter in the next menu win dow the 4 digit PIN You can find the PIN Next to the type label on the...

Страница 11: ...ensors with Bluetooth are found and created in the project tree 7 2 Connecting Connecting Select the requested sensor for the online para meter adjustment in the project tree Authenticate The window A...

Страница 12: ...value Storable values are for example Distance Filling height Percentage value Lin percent Scaled Current value Measurement reliability Electronics temperature When the instrument is shipped the measu...

Страница 13: ...in maintenance for the instrument because a failure is expected in the near future e g due to buildup Information The status messages are always active It cannot be deactivated by the user Failure Cod...

Страница 14: ...simulation Wait for the automatic end after 60 mins Tab 9 Error codes and text messages information on causes as well as corrective measures Out of specification Code Text mes sage Cause Rectificatio...

Страница 15: ...correct if necessary Voltage supply missing Check cables for breaks repair if necessary Operating voltage too low load resistance too high Check adapt if necessary Current sig nal greater than 22 mA...

Страница 16: ...nt consists of materials which can be recycled by specialised recycling companies We use recyclable materials and have designed the electronics to be easily separable WEEE directive The instrument doe...

Страница 17: ...stance between the lo wer antenna side and the product surface The reference plane for the measurement is also the lower antenna side 2 3 1 Abb 32 Data of the input variable 1 Reference plane 2 Sensor...

Страница 18: ...nding specifications are thus not possible 0 5 m 1 640 ft 10 mm 0 394 in 10 mm 0 394 in 5 mm 0 197 in 5 mm 0 197 in 0 1 2 Abb 33 Deviation under reference conditions 1 Reference plane 2 Measuring rang...

Страница 19: ...le gland Connection cable Configuration two wires one Kevlar cable braiding cover Wire cross section 0 5 mm AWG 20 Length 12 m 39 37 ft Min bending radius 25 mm 0 984 in with 25 C 77 F Diameter approx...

Страница 20: ...56 N 24 26 31 E France Plateau de Bure 44 38 01 N 05 54 26 E Floirac 44 50 10 N 00 31 37 W Germany Effelsberg 50 31 32 N 06 53 00 E Hungary Penc 47 47 22 N 19 16 53 E Italy Medicina 44 31 14 N 11 38 4...

Страница 21: ...21 10 Supplement NCR 21 4 20 mA 54408 01 190131 10 3 Dimensions NCR 21 9 5 mm 0 37 243 mm 9 57 43 mm 1 69 18 mm 0 71 72 mm 2 84 8 mm 0 32 G1 93 mm 3 66 Abb 34 Dimensions NCR 21 925 0374...

Страница 22: ...e you may not use this file except in compliance with the License You may obtain a copy of the License at http www apache org licenses LICENSE 2 0 Unless required by applicable law or agreed to in wri...

Страница 23: ...23 Notes NCR 21 4 20 mA 54408 01 190131 925 0374...

Страница 24: ...pplication practical use and operating conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior notice VEGA Grie...

Отзывы: