8 Diagnosis, asset management and service
NCR-21 4 … 20 mA
54408-01-190131
•
PC with PACTware/DTM
•
Control system with EDD
8.3 Asset Management function
The instrument features self-monitoring and
diagnostics according to NE 107 and VDI/
VDE 2650. In addition to the status messages
in the following tables there are more detailed
error messages available under the menu item
"
Diagnostics
" via app or PACTware/DTM.
Status messages
The status messages are divided into the
following categories:
•
Failure
•
Function check
•
Out of specification
•
Maintenance requirement
and explained by pictographs:
4
1
2
3
Abb. 31: Pictographs of the status messages
1 Failure - red
2 Out of specification - yellow
3 Function check - orange
4 Maintenance - blue
Failure:
Due to a malfunction in the instrument,
a fault message is output.
Function check:
The instrument is being
worked on, the measured value is temporarily
invalid (for example during simulation).
Out of specification:
The measured value is
unreliable because an instrument specification
was exceeded (e.g. electronics temperature).
Maintenance:
Due to external influences, the
instrument function is limited. The measurement
is affected, but the measured value is still valid.
Plan in maintenance for the instrument because
a failure is expected in the near future (e.g. due
to buildup).
Information:
The status messages are always active.
It cannot be deactivated by the user.
Failure
Code
Text mes-
sage
Cause
Rectification
F013
no measured
value availa-
ble
•
Sensor does not
detect an echo
during operation
•
Antenna system
dirty or defective
•
Check or correct
installation and/
or parameter
settings
•
Clean or
exchange pro-
cess component
or antenna
F017
Adjustment
span too
small
•
Adjustment not
within specifi-
cation
•
Change adjust-
ment according
to the limit
values (diffe-
rence between
min. and max.
≥ 10 mm)
F025
Error in the li-
nearization
table
•
Index markers
are not conti-
nuously rising,
for example
illogical value
pairs
•
Check linearisa-
tion table
•
Delete table/
Create new
F040
Error in the
electronics
•
Hardware defect
•
Exchanging the
electronics
•
Send instrument
for repair
F080
•
General soft-
ware error
•
Disconnect ope-
rating voltage
briefly
F105
Determine
measured
value
•
The instrument
is still in the
start phase, the
measured value
could not yet be
determined
•
Wait for the end
of the switch-on
phase
•
Duration up to
approx. 3 minu-
tes depending
on the version
and parameter
settings
F113
Communica-
tion error
•
EMC interfe-
rence
•
Remove EMC
influences
F125
Impermissib-
le electronics
temperature
•
Temperature of
the electronics
in the non-
specified range
•
Check ambient
temperature