9 Diagnosis, asset management and service
55
Fig. 30: Exchange cable or rod
Information:
Please maintain the specified torque so that the max. tensile strength of the connection remains.
6. Enter new probe length and if necessary the new probe type and then carry out a fresh ad-
justment (see "Setup procedure, Carrying out min. adjustment - Carrying out max. adjustment").
The rod or cable of the probe can be shortened individually.
1. Mark the requested length with mounted measuring rod.
2. Cable: Loosen the three pins on the gravity weight
Cable ø 4: hexagon 3
Cable ø 6, cable ø 8: hexagon 4
3. Cable: remove the pins
4. Cable: Pull the cable out of the gravity weight
5.
Shorten the cable/rod with a cut-off wheel or metal saw at the marking. Take note of the
specifications in the following illustration when shortening the cable.
6. Cable: shift the cable into the gravity weight (according to the drawing)
Plastic coated cable: remove coating according drawing to 70 mm (2.76 in).