National Fire Protection Association Standard
In accordance with NFPA 13 Standard from the National Fire Prevention Association as referenced in sections 12.1.4 and 11.1.7: High
Volume Low Speed (HVLS) Fans:
The installation of HVLS fans in buildings equipped with sprinklers, including ESFR sprinklers, shall comply with the following:
•
The maximum fan diameter shall be 24 feet (7.3 m).
•
The fan shall be approximately centered between four adjacent sprinklers.
•
The vertical clearance from the fan to sprinkler deflector shall be a minimum of 3 feet (0.9 m).
•
All fans shall be interlocked to shut down immediately upon receiving a water flow signal from the alarm system in accordance with
the requirements of NFPA 72- National Fire Alarm and Signaling Code.
I
f this installation will be performed outside the scope of work or not within the specifications of Big
Ass
Fans by customer’s request,
please provide specific details:
Check-In Procedure (cont.)
(for Big Ass
Fans Certified Installers Only)
Customer Signature:
Printed Name:
Date:
Contractor
Signature:
Printed Name:
Date:
The supervisor is to hold all documents until the job is complete and send all forms back to Field Service Manager. This will consist of
the service/work order, Check-In document, and Close-Out document. The installation crew will not receive payment until all forms are
signed by the facility manager and the supervisor. These documents will then be forwarded to the Field Service Manager at Big
Ass
Fans.
Please sign below if both parties agree that all aspects of this installation have been thoroughly explained and are of clear
understanding and agreement of the installation to be completed.
Содержание Pivot 180
Страница 1: ...INSTALLATION GUIDE For help call 1 877 BIG FANS or visit www bigassfans com Pivot 180...
Страница 46: ......
Страница 48: ......
Страница 50: ......
Страница 59: ......
Страница 60: ...1001340801 1001340801 2425 Merchant St Lexington KY 40511 1 877 BIG FANS WWW BIGASSFANS COM Rev L...