5
IDENTIFY URD CABLE USING STRCV
1.
Follow the “DC TRANSMITTER SET-UP AND TEST”
Procedure outlined on page 4.
2.
Ensure the power light is on, the blue pulse light is pulsing,
and the green short continuity light is illuminated. If the red
open light is on, turn the unit off, check your connections
and try again.
3.
Turn the STRCV on and place the tip on the wire close to
the transmitter to verify cable and direction of the pulse.
4.
At the test site, slowly approach the cable with the tip of
the STRCV. And identify the cable with the pulse going in
the same direction. Only the cable with the pulse pointing
in the same direction is the correct cable. Other cables may
show a pulse present but will be harder to pick up and will
pulse in the wrong direction.
5.
After testing is complete remove all equipment and restore
cable to its original condition.