Страница 1: ...L L 261 00 BM 1 25 INSTRUCTIONS MANUAL MANUEL D INSTRUCTIONS SPACE HEATER GENERATEUR D AIR CHAUD TITAN 750 TITAN 1000 FR EN ...

Страница 2: ...DING MATERIALS PAPER OR CARDBOARD AT SAFE DISTANCE AWAY FROM THE HEATER AS RECOMMENDED BY THE INSTRUCTIONS NEVER USE THE HEATER IN SPACES WHICH DO OR MAY CONTAIN VOLATILE OR AIRBORNE COMBUSTIBLES OR PRODUCTS SUCH AS GASOLINE SOLVENTS PAINT THINNER DUST PARTICLES OR UNKNOWN CHEMICALS WARNING NOT FOR HOME OR RECREATIONAL VEHICLE USE INSTALLATION OF THIS HEATER IN A HOME OR RECREATIONAL VEHICLE MAY R...

Страница 3: ...lt in gas leaks and fire or explosion from the leak The hose assembly must be protected from the traffic building materials and contact with hot surfaces both during use andwhile in storage WARNING Proper gas supply must be provided to the inlet of the appliance Refer to rating plate for proper gas supply pressure Gas pressure in excess of maximum inlet pressure specified at the appliance inlet ca...

Страница 4: ...N VENTILATEUR REFROIDISSEMENT 4 COMBUSTION CHAMBER CHAMBRE DE COMBUSTION 5 BURNER BRULEUR 6 THERMOSTATS L2 BOX BOITIER THERMOSTATS L2 7 HOISTING BRACKETS ÉTRIERS DE LEVAGE 8 SUPPORT HANDLE SUPPORT POIGNEE 9 WHEEL ROUE 10 BURNER BOX BOÎTIER BRÛLEUR 11 ELECTRICAL PANEL BOX BOÎTIER TABLEAU ÉLECTRIQUE 1 4 11 5 9 10 5 3 2 6 7 8 8 ...

Страница 5: ...INTAKE FOR PRE HEAT FILTER PRISE POUR FILTRE PRÉCHAUFFAGE f CABLE CLAMP FOR POWER CABLE PRESSE CÂBLES POUR CÂBLE D ALIMENTATION g TEMPERATURE CONTROLLER THERMORÉGULATEUR h BURNER LIGHT VOYANT BRÛLEUR i SAFETY THERMOSTAT RESET BUTTON L2 POUSSOIR DE RÉARMEMENT THERMOSTAT DE SÉCURITÉ L2 m BURNER RESET BUTTON LAMP TÉMOIN POUSSOIR DE RÉARMEMENT BRÛLEUR n ELECTRICAL PANEL BOX PANEL PANNEAU BOÎTIER TABLE...

Страница 6: ...a e a GAS SELECTOR VALVE VALVE SÉLECTEUR GAZ b MANIFOLD PRESSURE PORT PORT PRESSION BRULEUR c MANIFOLD PRESSURE REGULATOR RÉGULATEUR PRESSION d MAIN GAS VALVE SOUPAPE PRINCIPALE GAZ e INLET PRESSURE PORT PORT PRESSION EN ENTRÉE f SHUT OFF FIRING VALVE VALVE COUPURE ...

Страница 7: ... stop of the space heater In this case the heater will restart automatically when the required condition is restored The section TROUBLESHOOTING describes all possible operating faults and their possible remedies 2 CONDITIONS OF SUPPLY The heater is delivered with parts to be assembled and set as described in chapter 4 Heater body Burner Air distribution connector Any required accessories flue pip...

Страница 8: ...es and or chains of an appropriate size and length secured to the four suspension points Warning Make sure that the ropes and or chains form an angle not more than 5 with vertical to the ceiling that the ropes do not cross and that a different rope is used for each hook The minimum distance from surrounding walls and or ceiling must always be at least 1 metre The centrifugal fan has a panel B1 wit...

Страница 9: ...the thermostat plug c Close the plug again and plug it back into the panel Warning Never attempt to switch the heater on or off by connecting the room thermostat or other control devices to the electrical power line The installation and connection of all the other accessories are described in the specific instructions included with each accessory together with operating instructions The electrical...

Страница 10: ...rew onto the burner plate according to the instructions Secure the burner plate to the machine by using the 4xM8 screws and the D8 x D24 washers Open the box containing the gas valve group the gas selector valve group Connect the gas selector valve group to the burner use sealant approved for gas connection on thread L Insert the burner and fix it to the plate by tightening the nut supplied onto t...

Страница 11: ...Code CSAB149 1 In case of connection to a propane supply cylinder a the installation must conform with local codes or in the absence of local codes with the Standard for the Storage and Handling of Liquified Petroleum Gases ANSI NFPA 58 and the Natural Gas and Propane Installation Code CSA B149 1 b to determine size and capacity of the cylinder s and for any specific requirements consult your LP g...

Страница 12: ...UIREMENTS OF THE CAN CGA B149 1 OR CAN CGAB149 2 INSTALLATION CODES A conversion label shall be applied adiacent to the Rating Label THIS APPLIANCE HAS BEEN CONVERTED FOR USE AT AN ALTITUDE OF ___________ FEET ABOVE 2000 FEET Orifice size ______________________________________ Manifold pressure ______________________________________ Input rate ______________________________________ Date of convers...

Страница 13: ...n chamber has been heating for a few minutes the main fan will start up Warning The fan runs continuously in H V mode even when the desired room temperature has been reached and the burner turns off Warning In H mode the fan only runs when the combustion chamber is sufficiently hot Therefore when the desired room temperature has been reached the burner turns off and the fan keeps running only unti...

Страница 14: ...ature is factory set to 95 C with hysteresis of 5 C Red LED OUT 2 shows the operating state of the burner thermostat while the LED group indicates the current temperature compared to the set temperature if the red arrow at the symbol is ON it means that the temperature is below the set value and therefore the thermostat is ON i e the burner is ON if the green LED at the symbol 1 is ON it means tha...

Страница 15: ...thermostats as follows Remove any air outlet connection ducts Find the thermostats fixed to the internal panel of the space heater Clean with a dry cloth taking care not to cut or bend the capillary tube 6 7 CLEANING THE INTERIOR OF THE HEATER For thorough cleaning the heater can be cleaned and washed inside and outside with water It is however necessary to ensure that the electrical cable is disc...

Страница 16: ...n and off alternately and LED OUT 2 on the temperature controller is OFF when the burner goes off Burner thermostat has tripped due to overheating Check correct position of air distribution channels and opening of any flaps openings etc Remove any foreign bodies trapped in the air ducts or ventilation grilles The heater does not work the lamp on the electrical panel is on Manual reset safety therm...

Страница 17: ...NTROL LAMP LAMPE TEMOIN SECURITE DE SURCHAUFFE L1 BURNER THERMOSTAT setting 90 C THERMOSTAT BRULEUR régulation 90 C TA ROOM THERMOSTAT PLUG PRISE THERMOSTAT D AMBIACE RE2 DELAYED IGNITION RELAY RELAIS DE RETARD ALLUMAGE R ANTI CONDENSATION RESISTANCE RÉSISTANCE ANTICONDENSATION TM FANS TELE CONTACTOR TELERUPTEUR VENTILATEUR RM FANS THERMAL RELAY RELAIS THERMIQUE VENTILATEUR ST POWER LAMP LAMPE TEM...

Страница 18: ...and Canada Heat input BTU h 751 326 Manifold pressure in w c 2 08 Burner head position N 5 Burner Air setting N 5 3 Fuel consumption CFH 290 60 Altitude 2 000 4 500 ft above sea level Canada only Heat input BTU h 676 194 Manifold pressure in w c 1 92 Burner head position N 5 Burner Air setting N Max Fuel consumption CFH 261 54 Air flow cfm 9 417 2 Fan Thermostat Setting F 95 Burner Thermostat Sett...

Страница 19: ...put BTU h 1 017 795 Manifold pressure in w c 1 64 Burner head position N Burner Air setting N 8 Fuel consumption CFH 398 88 Altitude 2 000 4 500 ft above sea level Canada only Heat input BTU h 916 015 Manifold pressure in w c 1 52 Burner head position N Burner Air setting N Max Fuel consumption CFH 358 99 Air flow cfm 11 182 9 Fan Thermostat Setting F 95 Burner Thermostat Setting F 194 Power suppl...

Страница 20: ...L L 261 00 BM 20 25 ASSEMBLY INSTRUCTION NOTICE DE MONTAGE ...

Страница 21: ...L L 261 00 BM 21 25 FOOT HANDLE ASSEMBLY INSTRUCTION NOTICE DE MONTAGE DU PIED DE LA POIGNEE Mod 750 kBTU h ...

Страница 22: ...L L 261 00 BM 22 25 FOOT HANDLE ASSEMBLY INSTRUCTION NOTICE DE MONTAGE DU PIED DE LA POIGNEE Mod 750 kBTU h ...

Страница 23: ...L L 261 00 BM 23 25 FOOT HANDLE ASSEMBLY INSTRUCTION NOTICE DE MONTAGE DU PIED DE LA POIGNEE Mod 1 000 kBTU h ...

Страница 24: ...L L 261 00 BM 24 25 FOOT HANDLE ASSEMBLY INSTRUCTION NOTICE DE MONTAGE DU PIED DE LA POIGNEE Mod 1 000 kBTU h ...

Страница 25: ...L L 261 00 BM 25 25 BIEMMEDUE S p A Via Industria 12 12062 Cherasco CN Italy Tel 39 0172 486111 Fax 39 0172 488270 www biemmedue com bm2 biemmedue com ...