I
SOL
A
IR
M
ANUAL
I
NSTALLATION
Manual version 1.1 (07-04-2016)
en-11
en
2.4
Hanging the unit up
2.4.1 Suspension method
Example of an auxiliary structure
This manual assumes suspension from an auxiliary structure,
consisting of two horizontal beams positioned above the door.
You may also fix the units directly to the ceiling, or to another
horizontal structure, using the screw holes in the upper side
of the unit.
Warning:
w
Make sure that the structure from which the
unit is about to be suspended can bear at
least 4 times the weight of the unit.
See also:
2.4.2 Determine the location of the unit
• The unit should preferably be placed in the room where
the temperature is highest.
• Position the underside of the unit at the same height as the
top of the doorway.
• Position the discharge side of the unit as close to the door-
way as possible, to ensure optimum operation.
Note:
n
If the distance is greater than 5 cm., you are advised
to seal off the openings at the side. For this purpose,
you can order a side shield of plastic strips from
Biddle.
• Position the row of units centrally in relation to the door-
way.
• Units of different widths can be positioned in random
order.
• Make sure that the inspection and intake sides of the units
remain accessible for maintenance.
Warning:
w
Make sure that all units can freely take in and
blow out air across their entire width.