Section 3. ELECTRICAL CONNECTIONS
CONNECTING THE UNIT TO MAINS POWER
Installation cable sizing should always be done by a qualified electrician in
accordance with current regulations.
The suggested mains supply cables for Innovair are as follows:
water heated units, 3-core mains cable (Cu/PVC/PVC) size 1mm
2
Mains Supply Running Current
(Amps)
Starting Current
(Amps)
Water Heated 230v/1/50Hz
1.5
4.5
The electric’s control panel is located directly behind the main access panel.
Water - Thread the mains power cable through the cable gland on the LHS (RHS
on LH units). Wire to terminals L N E on the terminal block located at the LH end
of the electric control panel (RH end on LH units). See figure 9. Use cable ties
provided to secure cables and ensure they are not trapped when panel is
replaced.
Figure 9
The connection of on site wiring should be restricted to the designated
connection points, i.e. the provided terminal block etc. No electrical
connection should be made directly with the IQeco controller. Always read the
wiring diagram.
Transformer
Terminal Block
IQeco
Controller