![Biasi Riva Plus Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/biasi/riva-plus/riva-plus_installation-and-operation-instructions-manual_2748980015.webp)
Riva Plus Manual
15
The installation location chosen must:
•
Comply with all clearances listed below.
•
Provide suitable location for the exhaust and intake venting.
•
Not be installed in an unheated space.
•
Comply with all local codes and standards.
Note: Dimensions shown are minimums. Greater clearances will simplify installation
and service.
Figure 6.1
WARNING: Do not install the boiler on carpeting
If the boiler is to be installed in an enclosed room with no fresh air intake, the room must have
proper vent louvers installed. There should be two louvers, place each within 12” of the
ceiling and floor respectively. Each vent will have a free area of 54 square inches.
Outside
Air Opening
Air Opening
Each opening free area =
1 sq. inch per 2,000 BTU/h
0 to 12"
0 to 12"
Figure 6.2
When choosing an installation location insure the exhaust and intake pipes comply with
NFPA 54. The drawing on the next page illustrates the restrictions on exhaust locations.
3 . 0 i n
2. 0 i n
10.0
i n
2.0
i n
CLOSET INSTALLA TION
MINIMU M PER MANAN T
CLEARAN
CE
FR
ON TV IEW
SID
E V IEW CLOSET
INSTA
LLA
TION
CLOSET INSTALLA TION
SERV ICECLEARANC E
1 8
. 0 in
31.6 in
8 . 0 in
1 5 . 8 in
15.2 in
Note
: For boilers in an enclosed
space it is recommended to install
a CO detector in the boiler room.
6. Installation Location
Содержание Riva Plus
Страница 2: ...Riva Plus Manual 2...
Страница 14: ...Riva Plus Manual 14 5 1 Sequence of Operation...
Страница 20: ...Riva Plus Manual 20 9 Venting Cont...
Страница 50: ...Riva Plus Manual 50...
Страница 52: ...1796213550 17962 1355 0 4007 44A4 USA...