18
DIP value
LED „Sense“
Min. arc
duration TX_LWL1,
b3 - b0
0 1 2 3 4
duration
disable
1010
1 0 1 0 1
500 ns
200 ms
1011
1 1 1 0 1
700 ns
200 ms
1100
1 0 0 1 1
100 ns
500 ms
1101
1 1 0 1 1
300 ns
500 ms
1110
1 0 1 1 1
500 ns
500 ms
1111
1 1 1 1 1
700 ns
500 ms
The „minimum arc duration“ is a filter that prevents short glitches in the ns-range from
being detected by the sensitive logic of the overcurrent cut-out.
Glitches shorter than the set value are not recognised as overcurrents.
The „Duration TX_LWL1, disable“ specifies the length of time after an arc appears
during which there is no light in the fibre optic cable.
Adjusting sensiti-
vity of arc detec-
tion and duration
of rapid switch-
off signal
(continued)
Settings example
IO1 STAT
IO2 DYN
Threshold
Mode
Example DIP switch settings on the PLI10 board
DIP switch
Sets
DIP value
Actual value
Mode
Device characteristic 0001
Device characteristic V2
Threshold
Sensitivity
0011
600 ns min. arc duration,
20 ms duration TX_LWL1 Disable
IO1 STAT
I
OFFSET
1
1001
45 A
IO2 DYN
I
OFFSET
2
0000
0 A; maximum rise (case 3)