IMPORTANT

1. When making drain fitting connections to the drain pan, use a thin layer of Teflon paste, 
silicone or Teflon tape and install, hand tighten.
2. When making drain fitting connections to drain pan, do not overtighten. Over tightening 
fittings can split pipe connetions on the drain pan.

• Install drain lines so they do not block service access to front of the unit. Minimum clearance 
of 24 inches is required for filter, coil or blower removal and service access.
• Make sure unit is level or pitched slightly toward primary drain connection so that water will 
drain completely from the pan. (See Fig. 5)
• Do not reduce drain line size less than connection size provided on condensate drain pan.
• All drain lines must be pitched downward away from the unit a minimum of 1/8” per foot of 
line to ensure proper drainage.
• Do not connect condensate drain line to a closed or open sewer pipe. Run condensate to an 
open drain or run line to a safe outdoor area.

Fig5 Condensate drain trap

Содержание BMPE36CTL

Страница 1: ...1 Modelos BMPE36CTL BMPE60CTL BMPE72CTL Manual de usuario e instalaci n Unidades interiores de alta eficiencia 1 5 6 TR Refrigerante R410 A...

Страница 2: ...ion with installtion All phases of this installation must comply with NATIONAL STATE AND LOCAL CODES If additional information is required please contact your local distributor These instructions are...

Страница 3: ...ce Electrical wiring 4 1 Power wiring 4 2 Control wiring 4 3 Grounding 4 4 Electrical data Airflow performance Ductwork Refrigerant connections 7 1 Condensate drain tubing Air filter not factory insta...

Страница 4: ...ower wires can be safely removed from the blower assembly Failure to do so can cause electrical shock resulting in personal injuring or death Because of possible damage to equipment or personal injury...

Страница 5: ...les should be connected in fixed wiring The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube This appliance can be used by children aged...

Страница 6: ...ia Proposition 65 warnings are required for certain products which are not covered by the OSHA standards California s Proposition 65 requires warnings for products sold in California that contain or p...

Страница 7: ...supply air plenum and ductwork must be constructed of sheet metal as required by NFPA 90B The supply air plenum or duct must have a solid sheet metal bottom directly under the unit with no openings r...

Страница 8: ...tion of air volume to match any application 3 Speed motors provide selections of air flow to meet desired applications Top and side power and control wiring accessible screw terminals for control wiri...

Страница 9: ...r either side 24 36 60 72 Dimensions inch mm UNIT HEIGHT H IN mm MODEL SIZE UNIT WIDTH W IN mm UNIT LENGHT D IN mm SUPPLY DUCT A UNIT WEIGHT SHIPPING WEIGHT LBS kg 41 3 8 1050 46 1 2 1180 54 1 2 1385...

Страница 10: ...e ducted install duct flush with floor Use fireproof resilient gasket 1 8 to 1 4 in thick between the ducts unit and floor Set unit on floor over opening IMPORTANT NOTE Torque applied to drain connect...

Страница 11: ...ght wire bundle into top right breaker lug ensuring all strands of all wires are inserted fully into lug and no wire insulation is in lug Tighten lug as tight as possible while holding circuit breaker...

Страница 12: ...install coil in unit as shown for right hand air supply Rotate unit into the downflow position with the coil compartment on top and the blower compartment on bottom See Fig 3 Reinstall the indoor coil...

Страница 13: ...can be changed to horizontal right hand supply by removing the indoor coil and reinstalling 180 from original 3 4 Installation in an unconditioned space IMPORTANT There are two pairs of coil rails in...

Страница 14: ...ectrical Data In this section for ampacity wire size and circuit protector require ment Supply circuit protective devices may be either fuses or HACR type circuit breakers Power wiring may be connecte...

Страница 15: ...pigtails extending from top of air handler upflow position see Figure 3 Connections for control wiring are made with wire nuts Control wiring knockouts 518 and 7 8 are also provided on the right and...

Страница 16: ...1261 755 290 1 32 1394 815 304 1 39 1484 860 352 1 6 658 644 146 0 68 804 723 172 0 78 901 790 214 0 98 1186 778 277 1 26 1311 833 293 1 33 1403 873 341 1 54 618 688 139 0 65 761 759 166 0 76 853 815...

Страница 17: ...689 3 14 1901 974 885 4 02 1460 850 610 2 78 1550 893 680 3 11 1865 994 873 3 98 1460 850 610 2 78 1550 893 680 3 11 1865 994 873 3 98 1451 859 608 2 78 1545 900 679 3 1 1856 999 871 3 97 1451 859 608...

Страница 18: ...rtable living space An air velocity meter or airflow hood can give a reading of system CFM 6 Ductwork Field ductwork must comply with the National Fire Protection Association NFPA 90A NFPA 90B and any...

Страница 19: ...rills or sharp screw points can damage insulation on wires located inside unit Secure the supply and return ductwork to the unit flanges using proper fasteners for the type of duct used and tape the d...

Страница 20: ...e of 24 inches is required for filter coil or blower removal and service access Make sure unit is level or pitched slightly toward primary drain connection so that water will drain completely from the...

Страница 21: ...ompletely no leaks are found in drain line fittings and water is draining from the termination of the primary drain line 8 Air filter not factory installed External filter or other means of filtration...

Страница 22: ...arily lodge In the duct runs and at the supply registers Any circulated dust particles could be heated and charred by contact with the air handler elements This residue could soil ceilings walls drape...

Страница 23: ...MODEL B IN MODEL SIZE W IN mm D IN mm H IN mm 16 20 406 508 18 20 457 508 20 22 508 559 16 8 426 18 3 466 20 7 526 20 4 518 21 6 548 23 9 608 1 25 4 1 25 4 1 25 4 19 6 20 8 23 14 8 16 3 18 8 10 Wirin...

Страница 24: ...e the power fuse or the circuit breaker or the corresponding scale ampere Suggestion Thermostat choose KJR 23B or Non programmed eletrical thermostat series of Honeywell such as TH 5220D Wiring please...

Страница 25: ...black wire and connect with FAN terminal while medium speed red wire connect with M2 terminal 3 Low speed wiring Switch to low speed blue wire and connect with FAN terminal while medium speed red wir...

Страница 26: ...26 Fig 10 Indoor Unit Wiring Diagram for Electric Heat...

Страница 27: ...15A 3 14 3 12 2 18 4 18 36 15A 3 14 3 10 2 18 4 18 60 15A 3 14 3 10 2 18 4 18 72 15A 3 14 5 14 2 18 4 18 36 60 72 WITH 3 PHASE OUTDOOR UNIT Indoor Unit Power Phase Voltage frequency Lines Gauge Model...

Страница 28: ...y heating already installed and a different auxiliary heating unit is required the indoor unit A and indoor line diameters will be different These units must be wired and installed in accordance with...

Страница 29: ...29...

Страница 30: ...30 Notas...

Страница 31: ...31 Notas...

Страница 32: ...32 OFICINA CENTRAL Arias 1639 3 Piso C A B A C1429DWA TEL 54 11 4309 2000 www ecosmart bgh com ar MANMULTIPEVBGHBMPCTA01 ecosmart bgh ecosmart bgh BGH Eco Smart...

Отзывы: