background image

the screen   
 

 
Faulty motor/capacitor 
 

 
Check and if necessary replace 

Lock-out of appliance due to previous 
overheating 
 
 
 

Detect the cause of overheating 
Shut the appliance down 
Check air inlet and outlet 
Wait some minutes and restart the 
appliance 

E2 displayed on 
the screen 

The temperature probe is faulted or 
the connector for temperature probe is 
loosen 

Check and replace if the temperature 
probe if needed 
Check and replace the PCB if needed 

Motor runs, but the 
heater does not 
ignite and locks 
out after a short 
time   
 
E1 displayed on 
the screen   
 

Empty fuel tank, dirty or wrong fuel 
 

Remove wrong or dirty fuel 
Fill the tank with clean Diesel or kerosene 

Ignition fault, dirty or incorrect 
electrods position 

Check and clean electrods 

Fuel filter clogged   

Clean or replace fuel filter 

Burner nozzle clogged 

Clean nozzle blowing compressed air, 
replace if necessary 

Fuel viscosity increased at low 
temperature 

Mix Diesel with 10-20% kerosene   

Heater starts but 
combustion is not 
good 
 
 

Insufficient airflow into combustion 
chamber 

Check air inlet, fan, motor and air collar 
position, adjust it if necessary. 

Wrong fuel pressure 

Check fuel pressure, adjust it if needed 
   

Leaks in fuel line 

Check and fix fuel leaks 

Heater stops 
during operation 
 
Ambient 
temperature 
displayed on the 
screen   

The room temperature set on room 
thermostat has been reached 

Normal operation 
To start turn the temperature control knob 
clockwise on a higher setting   

Heater stops 
during operation 
 
E1 displayed on 
the screen 

Flame failure 

Check and remove the cause(s) of 
malfunction 
To reset, turn On/Off switch to 0 and then 
to I   
Call technical service if the problem 
persists 

Bad combustion 

Reduced airflow 

Overheating 

 
 

NINGBO BAOGONG ELECTRICAL APPLIANCE CO.,LTD. 

Add: FuHai Industrial Zone, Cixi Nongbo city, China 

PC.: 315332 

Tel:+860574-63682508 63682208 63682210 63682210 

Fax:+80-574-63682517 

E-mail:[email protected] 

Http://www.baogon.com

 

BGE reserves the right to make alterations to specifications, quantities, etc., for production or other reasons, subsequent to pu blication. 

©BGE. 2015 

 

 

 
 

Содержание BGO100A

Страница 1: ...B BGO70A 100A Instruction Manual Direct and Indirect fired Diesel Kerosene Heaters BGO 30B Indirect fired BGO 50B Indirect fired BGO 60B Indirect fired BGO 80B Indirect fired BGO 70A Direct fired BGO...

Страница 2: ...arranty or representation for any particular purposes The information is offered in good faith and with the understanding that any use of the units or accessories in breach of the directions and warni...

Страница 3: ...MAY CAUSE CARBON MONOXIDE CO POISONING WHEN INCORRECTLY USED E G INDOORS WITHOUT ADEQUATE AIR CIRCULATION OR IF NOT PROPERLY WORKING CO POISONING MAY LEAD TO DEATH GENERAL HAZARD WARNING FAILURE TO C...

Страница 4: ...V 50Hz Electrical Power Motor 250W 750W 750W 750W 430W 430W Pump Pressure Setting bar 10 0 10 5 11 5 10 0 10 5 10 0 Current Rating A 1 5 3 2 3 2 3 3 2 6 2 6 Fuse Rating T3 15A T3 15A T3 15A T3 15A T3...

Страница 5: ...h airflow from outside must be ensured Direct fired heaters are intended for use in outdoor open areas or in indoor well ventilated areas For indoor use provide permanent ventilation openings of at le...

Страница 6: ...ct the heater to a chimney or to an exhaust duct To get a proper draught in the chimney the exhaust gas path must rise Avoid any elbows and bends in the first part of the exhaust ducts for at least 3...

Страница 7: ...he appliance with wet hands or when either the heater or the power cable is wet If the supply cable is damaged it must be replaced by the manufacturer by a service agent or a similar qualified person...

Страница 8: ...Fig 6 Fig 2 Extract the burner head Fig 3 Fig 3 Whirl disc Clean the whirl disc Fig 3 using a brush and then blow compressed air on it To get good combustion the air flow openings in the whirl disc sh...

Страница 9: ...ecrease the pressure Fig 6 Air collar adjustment Fig 7 The air collar position is factory set and must be checked and adjusted by qualified technicians only Tampering with the unit may be dangerous HI...

Страница 10: ...connections 8 Wiring Diagram 9 Troubleshooting PROBLEM CAUSE REMEDY Motor does not start E1 displayed on No power or low voltage Check power line and voltage Check fuse and replace if necessary Fault...

Страница 11: ...th 10 20 kerosene Heater starts but combustion is not good Insufficient airflow into combustion chamber Check air inlet fan motor and air collar position adjust it if necessary Wrong fuel pressure Che...

Отзывы: