Technical data
3-1
3
Technical data
3.1
General characteristic features
•
Self-control to verify flawless
function of the device in
keeping with European
standard EN 298
•
Short switch off time
•
Failure output
•
Two externally selectable sensitivity levels
•
Relay output for sensitivity II active
•
Fully electronic construction
•
Tested by the German Technical Inspection Association
TÜV
•
Approved of by DIN DVGW
3.2
Electrical system, mechanical system,
function
Item
Value
Power supply
24 V DC
Consumption
approx. 150 mA
Preliminary fuse, built in
0,5 A, time lag
Operating temperature
0…+60 degrees
Intensity display
10-segments, LED bargraph
Status displays
LED, yellow for flame relay
LEDs, green for sensitivity level
LED, red for failure
Failur display
coded upper 5 LEDs from bar graph for
failure indication
Module failure detection
yes, output over relay contact
Sensitivity switching
Via external signal, 24V DC approx.
40mA or DIP switch S1.1