1. Install the damper in the duct.
2. Duct going through supporting construction, is fastened
using brackets. Seal according to applicable require-
ments, such as caulking with mineral wool, min 40 kg/
m
3
and fire stopping sealant.
3. If fire damper is not connected to the duct system, fit
non-combustible grilles designed for the damper on the
unconnected sides. The minimum distance between
the damper blade in the open position and the grille is
50 mm.
4. Install the thermal sensor with the sensor body in the air
flow without obstructing the movement of the damper
blade.
Installation in horizontal duct.
Damper’s fire resistance class: EI60 (ve i <–> o) S.
EC certificate 0402-CPD-SC0900-13
5. Duct is fastened/supported according to applicable
requirements.
6. Insulate the duct according to applicable requirements
using instructions from the insulation supplier, min.
80 mm and 55 kg/m
3
. Note that insulation must cover
the damper.
•
Minimum distance between dampers must be
200 mm.
•
Minimum distance to joist structure/wall must be
75 mm.
• The damper spindle may be installed in any position.
d+40
Duct
Duct
Seal acc. to
section 2
Support of duct,
see section 5
Seal with fire
stopping sealant,
e.g. Intumex AN
(Possible protective grille,
see section 3)
Insulation equivalent to
fire resistance class of the
supporting construction
Brackets
Max. 1000 mm
Installation instruction
EI60
Fire damper BSKC6