Duct detector RCKD

12-0553_ENG / Sept. 2017   teamfr

ont.se

Quick facts

•  Smoke detector for installation in ventilation ducts    
•  Optical detector head
•  Indication of a dirty detector head
•  0,6 m aluminium venturi pipe included 

Use

Indication of smoke in ventilation ducts. 

Design

Detector for installation in ventilation ducts, with optical 
 detector head, encapsulation and venturi pipe. RCKD 
gives indication of a dirty detector head. Power supply is 
from the control panel or control unit.

Material

Detector, white PVC with metal netting. Adapter housing 
with lid for single tube detector, made of clear ABS. 
Aluminum venturi tube.

Function description

The smoke detector has an optical detector head.
It also has an LED with two functions:
• red light indicates a tripped detector  

(detector, encapsulation)

• dirty detector is indicated with a green light  

(detector) or yellow light (encapsulation)

The detectors must be under continuous observation and 
must be cleaned at regular intervals to avoid false alarms.
The detector head is easy to change thanks to its bayonet 
fastening to the base. For detection in ventilation ducts, 

the detector head is mounted in an adaptor. One venturi 
pipe is then installed between the adapter and the duct to 
lead ventilation air into the detector head. In this way, the 
requirements for good fire protection can be complied with 
air speeds of 0.2 to 20 m/s. At lower air speeds, an auxi-
liary fan must be used. A metal reed/plastic strip is fitted 
for visual indication of flow through a duct detector.

Installation and location

Detectors are sensitive instruments, so care should be 
taken with their location. They should not be located close 
to sources of interference. The distance to the source of 
interference should be not less than 3 hydraulic diame-
ters upstream or 5 hydraulic diameters downstream from 
the source of interference. These distances are difficult to 
maintain, so 2 and 3 hydraulic diameters can be accepted 
in exceptional cases.
Duct detector RCKD is delivered with a 0,6 m venturi pipe 
that can easily be shortened. When the duct is wider than 
0,6 m the venturi pipe should go through the whole duct in 
accordance to our mounting instructions. This requires a 
longer venturi pipe, RBVR. 
RBMD installation shelf is used for circular ducts and for 
intact insulation of duct.
For location outdoors, in cold attics etc, the duct detector 
should be insulated. If the detector is concealed, light box 
RBLD should be installed.

Accessories

Installation shelf for duct detector  

RBMD

Venturi pipe for duct detector 

RBVR

Light box 

RBLD

Содержание RCKD

Страница 1: ...13 09 2017 www bevent rasch com RCKD Duct detector FIRE SAFETY ...

Страница 2: ...pipe is then installed between the adapter and the duct to lead ventilation air into the detector head In this way the requirements for good fire protection can be complied with air speeds of 0 2 to 20 m s At lower air speeds an auxi liary fan must be used A metal reed plastic strip is fitted for visual indication of flow through a duct detector Installation and location Detectors are sensitive in...

Страница 3: ...iring diagram with auxiliary fan Note Light box RBLD if installed is connected as follows RCKD between base terminals 3 and 4 Single connection Series connection Technical data System voltage optical 16 30V DC auxiliary fan 24V AC 75 mA Operation current 0 04 mA Alarm current 40 mA Service alarm current 10 mA Ambient temperature 10 to 55 C Permitted humidity 99 rF Max air speed 20 m s Service alar...

Страница 4: ...supply 24V 20 50 60Hz 24V 10 220 240V 50 60Hz Ambient temperature 30 to 50 C Safety temperature 30 to 75 C 24 hrs guaranteed safety Tripping temperature thermal sensor 72 C End position contacts load 300 mW min 1 mA 5V max 100 mA 250V After exceeding the above values it applies load 300 mW min 100 mA max 3 A 250 Sound level when opening approx 45 dB A Sound level when closing approx 62 dB A Chart ...

Страница 5: ...0 250 315 Size 100 400 500 630 45 dB 50 dB 55 dB 60 dB 65 dB 70 dB Correction of sound power level LWok in octave band Lwok Lw Kok Sound data Correction Kok Size Ø mm Centre Frequency Hz 63 125 250 500 1000 2000 4000 8000 100 4 6 7 12 17 24 26 33 125 5 5 8 14 22 25 27 35 160 5 4 8 13 17 20 28 34 200 3 6 10 14 15 19 27 40 250 1 11 15 20 22 23 29 37 315 2 8 11 12 13 19 23 29 400 2 8 14 12 15 22 30 4...

Страница 6: ...um distance between the damper blade in the open position and the grille is 50 mm 6 Install the thermal sensor with the sensor body in the air flow without obstructing the movement of the damper blade 7 Install the duct system according to applicable require ments Minimum distance between dampers must be 200 mm Minimum distance to joist structure wall must be 75 mm Installation instruction Fire da...

Страница 7: ...ation in horizontal duct Damper s fire resistance class EI60 ve i o S EC certificate 0402 CPD SC0900 13 5 Duct is fastened supported according to applicable requirements 6 Insulate the duct according to applicable requirements using instructions from the insulation supplier min 80 mm and 55 kg m3 Note that insulation must cover the damper Minimum distance between dampers must be 200 mm Minimum dis...

Отзывы: