Better Water LLC; rev. Jun 2016
Page 46 of 72
MediPac, Tank-Feed Operator Manual
FOR SERIES 6 VALVES: (for older models)
1.
Ensure both hot and cold water supplies are open,
and the RO is running in good water quality.
2.
Turn the Adjustment Knob clock-wise until it is all the
way in and can no longer be turned. Observe the
Temperature Gauge to verify that the water temperature
is changing.
3.
Turn the Adjustment Knob counter-clockwise, four complete turns.
Observe the Temperature Gauge to verify that the water temperature is
changing.
4.
Repeat steps 2 and 3, two more times.
5.
Turn Adjustment Knob clock-wise to adjust the water temperature to the desired setting, by
verifying the Temperature Gauge reading. Allow time for the newly blended water to be pulled
through the Blend Valve and for the Temperature Gauge to stabilize.
6.
The final water temperature setting should be based on a verified water temperature of 77ºF at
the RO.
7.
Any further adjustments should be done by turning the Adjustment Knob in small increments.
Allow time for the newly blended water to be pulled through the Blend Valve and for the
Temperature Gauge to stabilize.
FOR SERIES 7 VALVES:
1.
Ensure both hot and cold water supplies are open,
and the RO is running in good water quality.
2.
Loosen the Locking-Nut on the Adjustment Bolt, by
turning it counter-clockwise until it can no longer be turned.
3.
Using a wrench turn the Adjustment Bolt clock-wise until
it is all the way in and can no longer be turned. Observe the
Temperature Gauge to verify that the water temperature is
changing.
4.
Turn the Adjustment Bolt counter-clockwise, four complete turns.
Observe the Temperature Gauge to verify that the water temperature is changing.
* CAUTION: Turning the Adjustment Bolt fully counter-clockwise will remove the Bolt from the
Blend Valve. If this occurs simply replace the bolt.
5.
Repeat steps 3 and 4, two more times.
6.
Turn Adjustment Bolt clock-wise to adjust the water temperature to the desired setting, by
verifying the Temperature Gauge reading. Allow time for the newly blended water to be pulled
through the Blend Valve and for the Temperature Gauge to stabilize.
7.
The final water temperature setting should be based on a verified water temperature of 77ºF at
the RO.
8.
Once the desired temperature has been achieved, hand-tighten the Locking Nut on the
Adjustment Bolt, by turning it clockwise until it can no longer be turned to ensure the Adjustment
Bolt will stay in the final position set.
Series 6
Valve
Series 7
Valve
Adjustment
Knob
Adjustment
Bolt
Locking-Nut
(Under the