The Fortress’s BestDock communication slot accepts optional communication cards, like the
internal BestLink SNMP/WEB adapter. The insertion of a card into the BestDock communication
slot replaces the normal communication channel from the Fortress’s DB-9 Communication Port.
The DB-9 port becomes the connection point for configuring the card in the BestDock.

Troubleshooting

If you have a question or problem, the troubleshooting table may help. (See Table 3.) If you need
assistance, phone Best Power’s Worldwide Service or your local Best Power office. Please have
the model number and serial number (located on the rear of the unit) available.

If the unit must be returned, Best Power will give you a Return Materials Authorization (RMA)
number. Phone Best Power for an RMA number before returning the unit for any reason.

Problem

Possible Reasons

What To Do

Yellow 

BATTERY

LED on,

Green 

LINE

LED off,

one beep every 10seconds.

1.  Utility power outage.
2.  Loose plug.

3.  Tripped circuit breaker.
4.  Power cord failure.

1.  Wait for power to return.
2.  Make sure the power cord is 

connected.

3.  Reset the circuit breaker. 
4.  Phone Best Power’s Worldwide

Service.

Yellow 

BATTERY

LED on,

Green 

LINE

LED off,

two beeps every 10 seconds.

Very low battery voltage.

Plug the unit into a working wall outlet
for at least 8 hours to allow the batteries
to charge. After recharge, if the Fortress
will not operate on batteries, or Fortress
beeps twice every 10 seconds on batter-
ies, phone Best Power’s Worldwide
Service. 

Yellow 

WARNING

LED on,

Green 

LINE

LED on,

three beeps every five minutes.

Yellow 

OVERLOAD

LED on,

one beep every second.

Unit has failed the battery
test

The power required by the
equipment is too high.

Turn the unit off and then on to reset 
the “Replace Battery” alarm and LEDs.
Replace the battery. See “Replacing the
Batteries” on page 10.

1.  Remove load equipment.
2.  Reduce load level until the beeping

stops.

Yellow 

WARNING

LED on.

Continuous beep.

1.  Output short circuit.
2.  UPS Fault

1.  Remove load and reset UPS.
2.  Phone Best Power’s Worldwide

Service.

Table 3: Troubleshooting

Содержание Fortress 1050 VA

Страница 1: ...USER GUIDE Fortress Rackmount 750 VA 1050 VA 1425 VA 1800 VA and 2250 VA...

Страница 2: ...ge must be limited to 3 mA on the U model and 2 5 mA on the E model If you do not know the load leakage current replace the UPS power cord with a power cord that uses a lock ing plug with a minimum ra...

Страница 3: ...F o r t r e s s Rackmount 750 VA 1050 VA 1425 VA 1800 VA and 2250 VA User Guide FSS 0388B Copyright 1998 Best Power All rights reserved...

Страница 4: ...he unit If you prefer you can contact Best on the World Wide Web to get more product information Best s toll free Fax on Demand service is also available 24 hours a day to give you access to technical...

Страница 5: ...eplacing the Batteries 10 Battery Replacement Instructions 11 Communication Port 12 DB 9 Pinouts 13 Specifications 13 Warranty 15 Appendix A Adjusting Voltage Settings 17 Best Power Offices 20 Tradema...

Страница 6: ...bove 25 Celsius 77 Fahrenheit recharge the batteries more often CAUTION Whenever the Fortress is On there may be dangerous voltage present at the unit s outlets This is true because the unit s battery...

Страница 7: ...panel LEDs and an audible alarm keep you aware of the unit s sta tus Use the drawings on this and the following page to identify features of the unit Line Buck boost Battery Mode Load or Battery Char...

Страница 8: ...ULT 1050 1425 E 1050 1425 U 1 Status Indicators 8 5 15 Outlets 1800 and 2250 2 On Standby Button have breaker 3 Alarm Program Button 9 5 20 Outlets 2250 has breaker 4 Battery Access Panel 10 L5 30 Out...

Страница 9: ...hardware from electronics distributors below the intended rack location for the Fortress Secure the shelf or brackets at both the front and back of the rack using bolts nuts and washers Carefully lift...

Страница 10: ...main on If the unit beeps or if the top light does not remain on even though input power is available from the wall outlet go to the Troubleshooting section 4 Switch off the equipment you want to prot...

Страница 11: ...s labled Site Wiring Fault lights to indicate a wiring fault in the circuit to which the Fortress is connected If this LED is on the outlet needs to be checked and repaired by an electrician Do not us...

Страница 12: ...is running on battery power Output Overload Refer to Tables 2 and 3 Replace the Battery or UPS Fault Refer to Tables 2 and 3 Blinking The unit is boosting or bucking utility power Boost Automatically...

Страница 13: ...onds 1 Utility power outage 2 Loose plug 3 Tripped circuit breaker 4 Power cord failure 1 Wait for power to return 2 Make sure the power cord is connected 3 Reset the circuit breaker 4 Phone Best Powe...

Страница 14: ...s could fall into the UPS Never allow any tool to contact both a battery terminal and the UPS cabinet or another battery terminal Do not lay tools or metal parts on top of batteries To ensure continue...

Страница 15: ...plug the protected load equipment from the Fortress Then turn off the Fortress and disconnect the line cord 3 Use the drawings below to identify the location on the battey pack in the model Fortress t...

Страница 16: ...l to the front panel 11 If you followed the option in step 2 Reconnect the line cord to the Fortress and turn the unit on 12 Reconnect the load equipment Switch on the protected load equipment one pie...

Страница 17: ...n 9 Unused Contacts consist of open collector circuits capable of switching up to 30 VDC 6 mA resistive load Specifications Best Power reserves the right to change specifications without prior notice...

Страница 18: ...me to 95 of capacity 750 VA 1050 VA 1425 VA 1800 VA and 2250 VA 3 hours 1425 VA 7 hours with output fully loaded Recharge time is lower with reduced load Overcurrent Protection on line All Models Circ...

Страница 19: ...he PURCHASER must promptly notify BEST POWER in writing within the duration of the warranty or not later than one month after expiration of the warranty BEST POWER s obligation under this warranty is...

Страница 20: ...the Product beginning with the date of sale to the initial retail purchaser subject to the following conditions This warranty is applicable only to the initial retail purchaser hereinafter called PURC...

Страница 21: ...above limitation on duration of implied warranties may not apply to you Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusio...

Страница 22: ...en input voltage rises to 130 the Fortress begins to decrease buck the output voltage With 146 volts input or higher the Fortress switches to battery power 3 Use the appropriate table on the next page...

Страница 23: ...146 156 1 2 5 90 104 128 146 156 Table 4 Voltage Settings for U Models 750 1050 1425 1800 and 2250 VA Table 5 Voltage Settings for E Models 750 1050 1425 and 2250 VA 270 244 230 200 180 3 4 6 284 250...

Страница 24: ...NGAPORE 188647 Telephone 65 430 6168 FAX 65 430 6170 Sola Australia Ltd 13 Healey Road Dandenong Victoria 3175 AUSTRALIA Telephone 61 3 9706 5022 FAX 61 3 9794 9150 BEST House Wykeham Industrial Estat...

Страница 25: ...is equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmfu...

Страница 26: ...FSS 0388A...

Отзывы: