3.6.6.2
Emergency extended parameters
In the case of being a DALI emergency, some extra parameters and functionalities are available by doing click on emergency
parameters (check the manufacturer information).
The following window shows the specific internal status of the emergency and allows to execute two different tests: battery
autonomy and normal function test. The results of the tests and many other important indicators are shown if the DALI
emergency supports them.
3.7
Summary: recommended procedure
The DALI installation on-line commissioning can be done by using all the functions that have been explained before. As
summary, the recommended procedure of a DALI installation commissioning is the following:
Download the individual address to the gateway with the ETS.
Open the plug-in application from the parameters window and change to on-line mode.
Check that every DALI node (EVG) is correctly connected by sending a switch on telegram to broadcast
If every DALI ballast is correctly connected, do click on New initialization. The DALIK gateway will carry out a
progressive scan of the DALI line assigning an aleatory address to each non-addressed node (EVG).
Use the System extension function if a new ballast has been connected.
Set all the behaviour parameters, groups and scenes of each DALI node (EVG).
Do click on the ok button to save the configuration. The communication objects of every DALI ballast and group will
be shown now in the ETS.
Do the assignment of the communication objects to KNX group addresses.