DALIK
- Gateways
Programming manual
v1.4.3
www.besknx.c
z
19
3.6.1
DALI commissioning
3.6.1.1
New initialization
The “New initialization” function is used the first time with no commissioned or addressed DALI installations.
The DALIK gateway will search for every connected DALI ballast by carrying out a progressive scan of the DALI line,
identifying all the devices and assigning a DALI address to each of them. The time taken for the whole search can vary
depending on the amount of DALI devices connected.
The devices detected and addressed by the gateway will be included in its DALI lights/groups tree automatically.
By pressing OK, the corresponding objects of each detected and addressed DALI node (EVG) will be shown in the ETS
objects table.
By using this function, the current configuration of the gateway will be lost and every DALI address may change.