background image

-4-

  2. Lower the unit into place allowing it to rest on the 

    mounting plate.  The unit flange should rest above the 

    mounting plate flange.

  3. After the unit is securely seated to the mounting plate,   

  install the locking screws along the bottom flange.  

  

See FIGURE 4.

C.

  Proceed to 

Section V-ELECTRICAL CONNECTIONS

IV. SUSPENDED MOUNTING 

(Ceiling Suspension)

A.

 When the unit is top mounted, the wall mounting plate is   

designed to store on the back of unit for future use. 

B.

  Four (4) factory installed #10-24 threaded inserts are located 

on the top of the unit for top suspension mounting. 

 

See FIGURE 5.

C.

  Determine the exact mounting location of the air curtain. 

D.

 Install #10-24 threaded rods, or other suitable hardware at a 

location sufficient to support the air curtain. The mounting 

hardware (supplied by others) must be capable of sup-

porting a minimum of three times the net weight of the air 

curtain. See 

WEIGHT CHART, TABLE 1.

E.

  Attach #10-24 threaded rods, or other suitable hardware to 

the top mounted threaded inserts.

F.

  Proceed to 

Section V-ELECTRICAL CONNECTIONS

V. ELECTRICAL CONNECTIONS

All electrical wiring and connections 

MUST

 be performed by 

qualified personnel in accordance with the National Electri-

cal Code ANSI/NFPA No. 70 (latest edition) or, in Canada, the 

Canadian Electrical Code, Part 1-C.S.A. Standard C22.1 and local 

codes and regulations.  Check the electrical rating nameplate 

on the top of the air curtain for supply voltage and current 

requirements.  

A

.  A separate line voltage supply with a suitable branch  

 

  circuit protection device should be run directly from the    

  main electrical panel to the air curtain. A disconnect switch  

  for each branch circuit is a required part of this installation.   

B.

  All field wiring must be copper with a minimum insulation  

  of 60° C within approved conduit. If any of the wire  

 

  supplied with the air curtain must be replaced, it must be  

  replaced with copper wiring with a minimum insulation of  

  90° C.

C.

  On top of the air curtain, remove the wiring compartment  

  cover.  

See FIGURE 6.

D.

  Remove the required knockout(s) and connect the power  

  supply to the air curtain.  Connect all supply and control    

  circuit wires according to the wiring diagram provided. 

NOTE:  For Electrically Heated air curtain(s) provided with 

the optional remote thermostat:

  mount and wire the 

thermostat according to instructions and wiring diagram.

NOTE:  For Electrically Heated air curtain(s)

 - Overheating 

protection is provided by auto reset thermal cutouts built into 

the heater coil assembly (see the wiring diagram, located in 

wiring tray).

VI. OPERATING INSTRUCTIONS

A.  GENERAL OPERATION

  1.   The air curtain can be directly operated by using the

     rheostat variable speed switch:

 

  

Series# PE06

 

- Unheated units use a remote mounted   

  rheostat variable speed switch that is shipped loose and  

  is located in the red bag.

 

  

Series# PT06

 - Heated units include a built-in rheostat  

  variable speed switch and a built-in heat on/off switch  

  on the bottom of the air curtain. Units ordered with 

     a remote mounted rheostat variable switch have no    

FIGURE 3 - Positioning of Mounting Plate

FIGURE 4 - Attaching Unit to Mounting Plate

Locking Screws

Mounting Plate

Lower Lip

FIGURE 5 - Suspended Mounting

Suspension Rods

Side View

#10-24 Threaded Insert

1" max.

Window Opening

Mounting

Plate Holes

Содержание Pass-Thru 6 Series

Страница 1: ...III WALL MOUNTING 3 IV SUSPENDED MOUNTING 4 V ELECTRICAL CONNECTIONS 4 VI OPERATING INSTRUCTIONS 5 VII MAINTENANCE AND CLEANING 5 VIII SERVICE 6 IX TROUBLESHOOTING 7 X WARRANTY 8 Installation Mainten...

Страница 2: ...ving jurisdiction including fire rated construction See page 4 ELECTRICAL CONNECTIONS NEC Code ANSI NFPA No 70 E When cutting or drilling into wall or ceiling do not damage electrical wiring and other...

Страница 3: ...th of the unit See FIGURE 2 C Do not block obstruct the air intake grill Insufficient airflow can cause the unit to overheat D Electric heated air curtain s shall 1 Have a minimum clearance of at leas...

Страница 4: ...ion device should be run directly from the main electrical panel to the air curtain A disconnect switch for each branch circuit is a required part of this installation B All field wiring must be coppe...

Страница 5: ...C AIR STREAM SPLIT ADJUSTMENT 1 With the air curtain operating and the window is in its full open position check to see that nothing is obstructing the air flow at the discharge nozzle vanes 2 Find th...

Страница 6: ...ned at least twice a year Your particular application theamountofdirtanddustintheair andlocation of the unit s will determine how often your unit s will need to be cleaned and serviced All motors have...

Страница 7: ...ken fan hub Shaft rotating inside fan Broken Loose coupling Selector switch is in OFF position Door limit switch not operating Air directional discharge vanes misadjusted Inadequate intake clearance B...

Страница 8: ...nse or liability for repairs made outside its factory without proper written consent from its service manager nor for any transportation charges on apparatus returned to the factory without written au...

Отзывы: