VII. OPERATING INSTRUCTIONS

Figure 9

20˚

AIR

Discharge 
Nozzle

A

IR

 

INTERIOR

EXTERIOR

3"

12"

Handkerchief

A

IR

 

B.

 

STEAM AND HOT WATER HEATED MODELS

 

The coil solenoid may either be controlled through 

the Intelliswitch™ or independently. The Intelliswitch™ 

is capable of providing the same voltage used for the 

motor to power a solenoid up to a 5 amp load on the 

call of heat.  The heater circuit may be controlled by the 

unit mounted sensor, a remote mounted thermostat or 

manually through the Intelliswitch™ located on bottom 
access cover of the air curtain

 

Piping should be done in 

accordance with local codes, regulations and standard 

practices.  Connect the building system supply and return 

to the 1” MPT nipples on the  heating coil. 

See Figure 8.

FIGURE 8 - Steam/Hot Water Connections

A. GENERAL OPERATION

This air curtain comes with a built-in Berner Intelliswitch™ 

Digital Controller to operate the fan activation, fan speed 

selection, and heat activation.  The air curtain must be properly 

installed before it is used.

1. 

For detailed instructions on how to operate the  

 

 

Intelliswitch™ and select from a list of standard modes  

 

of control, proceed to the following pages: 

 

   

Quick Start Operation Guide, page 9

 

   Frequently Asked Questions (FAQs), page 11

 

NOTE: For a Detailed Programming Guide, go to 

 

www.Berner.com/Intelliswitch

2. 

Unheated units will have the fans activated by a door 

switch or sensor. The unit speed can be selected from 

the Intelliswitch™ display. 

3. 

Heated units will have fans activated by a door switch 

or sensor, but may also be activated by the thermostat 

in Comfort Plus Mode. The unit speed can be selected 

from the Intelliswitch display. 

4. 

To operate using the

 

Berner Air Curtain App

  

NOTE: The air curtain must have been ordered 

from the factory with the wi-fi controller to use this 

option.  The wi-fi controller allows air curtain(s) to 

be programmed & operated via smart phone.

 

 

Requires on-site, secure wi-fi connection (provided by 

others). 

 

 

Download the “Berner APP” to your smart phone from 

the Google Play store.  Follow the prompts.  

Berner 

recommends having the on-site user(s) set-up the Berner 

App on his/her smart phone.

 

B. AIR STREAM ADJUSTMENT

 

1.   With the air curtain operating and the door in its full 

open position, check to see that nothing is obstructing 

the airflow at the discharge nozzle vanes. 

 

2.   Find the air stream split location. Hold a handkerchief 

by its corners, approximately 12”  above the floor. 

Gently move the handkerchief back and forth in the 

doorway. Make sure the air is being directed to both the 

inside and the outside. 

See Figure 9.

 The split location 

is indicated where the handkerchief is vertical with 

minimal or no fluttering.

 

3.   The split location should be approximately 3” outside 

the doorway. If necessary adjust the discharge nozzle 

vanes by de-energizing the unit, loosening the nozzle 

vane locking screws and adjusting vanes.

Содержание AHD10

Страница 1: ...ING INSTRUCTIONS 7 INTELLISWITCH QUICK START OPERATION 9 FAQ s FREQUENTLY ASKED QUESTIONS 11 VIII MAINTENANCE AND CLEANING 8 IX SERVICE 8 X TROUBLESHOOTING 13 XI APPENDIX A SERIAL NETWORK CONNECTION P...

Страница 2: ...aving jurisdiction including fire rated construction See page 6 ELECTRICAL CONNECTIONS NEC Code ANSI NFPA No 70 E When cutting or drilling into wall or ceiling do not damage electrical wiring and othe...

Страница 3: ...ace add locking screws 2 Locking Screws One In Each Corner Mounting Plate 45 Lip and Rubber Vibration Gasket Discharge Nozzle Before hanging check to see what the clearance is above the door 6 minimum...

Страница 4: ...rway a door opening device etc the effectiveness of the air curtain will be greatly reduced See Figure 2 B For optimum performance the bottom of the air curtain discharge nozzle should be no more than...

Страница 5: ...2 Lower the unit into place allowing it to rest on the lower lip of the mounting plate 3 After the unit is securely attached to the mounting plate re install the two 2 locking screws at the bottom cor...

Страница 6: ...e temperature is to be measured the sensor may be left on the endplate or positioned elsewhere Do not put any clamps on the rubber coated tip D Remove the junction box cover E Connect all supply and c...

Страница 7: ...ts will have the fans activated by a door switch or sensor The unit speed can be selected from the Intelliswitch display 3 Heated units will have fans activated by a door switch or sensor but may also...

Страница 8: ...ps head screws on the bottom of the unit Vacuum and scrape if necessary to remove the build up of dirt and debris The motor s are permanently lubricated and require no additional lubrication Re instal...

Страница 9: ...to run after the door closes Start Time Programmable time of day air curtain becomes active Stop Time Programmable time of day air curtain stops running T Stat Mode Set only heat or heat fan Set Time...

Страница 10: ...ir curtain turns off Door opens The air curtain activates Door shuts The air curtain continues to run Door opens The air curtain is off Door shuts The air curtain is off OFF 5 Standard Mode of Operati...

Страница 11: ...e panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot be locked securely fasten a prominent warning device s...

Страница 12: ...curtain is heated make sure that the thermostat isn t wired to the door switch leads Door switch leads are blue and labeled 9 10 Q How can I check the door switch to be sure it s working A The Intelli...

Страница 13: ...FANS ARE NOT ROTATING MINIMUM AIR ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN SYMPTOMS REMEDY CAUSE Broken or damaged flexible hub Shaft rotating inside fan Selector switch is in off positio...

Страница 14: ...operated in a network there are three options available under the Programming Menu that manage how they interact with each other Door Switch door Thermostat temp Stand By Stby Each option can be set t...

Страница 15: ...PURE mode operation When the door opens The air curtain and if applicable the heater s activate and run at set speed When the door closes for heated models The PURE mode allows for the air curtain to...

Страница 16: ...iability for repairs made outside its factory without proper written consent from its service manager nor for any transportation charges on apparatus returned to the factory without written authorizat...

Отзывы: