5.3
Calibration of travel limits
Cam-block detail
To stop the movement at end positions, the AT SWITCH actuator
features a set of cams integrated as a cam block. Cams trip switches
to switch off the power at end positions, or for signaling.
The cam block is made up of 4 cams.
Each one has a specific function and
trips a specific switch.
Each cam can be calibrated thanks
to a screwdriver imprint on the top
of
the
cam
block.
The
correspondence between a cam and
its screwdriver imprint can be
determined thanks to numbers and
colors (see figure opposite).
Rep.
Color
Function
1
White
Counterclockwise (usually OPEN) travel limit
2
Black
Clockwise (usually CLOSED) travel limit
3
Beige
Counterclockwise signaling
4
Gray
Clockwise signaling
Except for specific valve configurations:
•
Clockwise
direction generally matches
closing
direction.
•
Counterclockwise
generally matches
opening
direction.
3
2
1
4