English
7
6 TRAVEL LIMIT SETTINGS
The actuator is factory-set for a 90°travel.
It features 2 devices to limit the travel:
•
Cams trigger switches to switch off power at an end position or
to signal a position
.
•
Mechanical stops mechanically block rotation to protect the valve
in case of over-travel.
They must not be used as travel limits.
Setting a single cam
The cam rotates as the
output shaft and triggers a
switch by pushing on its
lever.
Cams orientation are factory
pre-set, yet you can still re-
adjust them upon
the
installation if necessary.
Rep.
Function
Status before installation
1
Clockwise travel limit
Pre-wired, cam pre-set
2
Counter-clockwise travel limit
Pre-wired, cam pre-set
3
Clockwise signalling
To wire, to set
4
Counter-clockwise signalling
To wire, to set
How to adjust a single cam
At the desired position of the actuator output:
1) Turn the setting screw of
the corresponding cam
with a flat-head or a
Phillips-head screwdriver.
The cam disk is then turning.
2) Set the cam disk until you
hear a click from the
switch. It indicates the
triggering of the switch.
Make sure the cams contact the switch according to their proper
direction of travel, otherwise you could damage the switch.
8
Содержание AQ1L
Страница 1: ...AQL Range Start Up Guide SUG_17002 Ind A Art 5100465...
Страница 2: ...TABLE OF LANGUAGES 1 English 3 2 Fran ais 3 3 Espa ol 5 4 Italiana 7 5 Deutsch 7 2 49 37 25 13 3...
Страница 62: ...NOTES...
Страница 63: ...NOTES...