6
400E-DP-Y
Model 400E-DP Components List
4.
Placing in Service/Resetting
The Dry Pipe valve and the control trim shall be placed in Service in accordance to the most recent IOM procedures for the
specific model.
4.1
Close the supply Isolating Valve.
4.2
Close the emergency release valves.
4.3
Apply supervisory air pressure to the system’s piping and set the pressure at 2.5 ±0.1 barg (36.5 ±1.5 psi) .
4.4
Close All Drain Valves.
4.5
Open the priming-line valve, pull the URV-M reset lever, this allows upstream water pressure to fill the Water
Control Valve’s control chamber.
4.6
When the control chamber pressure gauge indicates full upstream pressure and is no longer rising, the release system
is reset.
4.7
Open the downstream Drain Valve to drain any water from the downstream side of the valve.
4.8
Slowly Open the supply Isolating Valve and check that no water flows into the system.
The system is now operational and in a standby mode.
Item Description
Qty
Note
1
400E-Y Water Control Valve
1
1
1A
Alarm Test Valve 1/2"
1
2A
Gauge Valve 1/4"
3
2B
Restriction Orifice
1
3A
Pressure Gauge 4"
3
2
4B
Priming Strainer 1/2"
1
5A
Drain Valve
2
4
7B
Priming Check valve 1/2"
1
11A
Alarm Shutoff Valve 1/2"
1
15B
Manual Emergency Release
1
18B
Priming Valve - 1/2" Ball Valve
1
26B
Hydraulic Relay Valve (HRV)
1
F
Fittings and Tubing
3
U
URV-M w/ Manual Reset
1
Optional Accessories
P
Water-flow Alarm Pressure Switch (PSH)
P2
Low Pressure Switch (PSL)
AC
Automatic Water Drain Valve
I
Valve Visual Position Indicator
S
Valve Limit Switch
W
Water Motor Alarm
AMD
Air Maintenance Device
1C
Air Pressure Regulator
2C
Restriction Orifice
3C
Ball Valve
4C
Strainer
5C
Ball Valve
Notes:
(1) Suitable for Vertical or Horizontal installation
(2) UL-Listed, FM approved
(3) Fitting material: Galvanized/S.S or corrosion resistant equivalent
(4) For 1½ & 2”: ¾” Drain Valve; 3”: 1½” Drain Valve ; 4” and larger: 2” Drain Valve
Содержание 400E-Y
Страница 1: ...1 400E Y Deluge Valve Bermad 400E Y Torrent Deluge Valve Installation Operation Maintenance Manual IOM...
Страница 30: ...1 400E DP Y 400E DP Y Torrent Dry Pipe Valve Installation Operation Maintenance Manual IOM...
Страница 34: ...5 400E DP Y 3 1 1 Model 400E DP trim illustration Dry Pipe Valve...
Страница 38: ...1 400E Y Pre Action 400E Y Torrent Pre Action Systems Installation Operation Maintenance Manual IOM...
Страница 70: ...IOM Model 43T Pressure Relief Valve PAGE 9 OF 10 Figure 3B GA Drawing for Size 8 10...