4
400E-Y Deluge Valve
3.
Operation
3.1
Hydraulically Controlled
Bermad Hydraulically Controlled Deluge valve is suitable for automatic or remote controlled water or foam systems
that include a wet pilot-line with closed fusible plugs (thermal releases) and piping systems .The typical wet pilot-
line is installed in a covered area and connected to the valve trim. In fire conditions, operation of a release device
on the wet pilot line opens the Deluge Valve, allowing water to enter the system piping.
NOTE
: Wet pilot line height should not exceed maximum elevation above valve see attached graph.
3.1.1
Model 1M Trim Illustration: Hydraulically Controlled with EasyLock Manual Reset
Item Description
Qty Note
1
400E-Y Deluge Valve
1
5
1A
Alarm Test Valve 1/2"
1
8
2A
Gauge Valve 1/4"
2
8
3A
Pressure Gauge 4"
2
2, 8
4B
Priming Strainer 1/2"
1
5A Drain
Valve
1
1, 4, 8
15B Manual
Emergency
Release 1
1, 9
18B
Priming Valve 1/2" Ball Valve
1
19A
Drip Check Device 1/2"
1
8
F
Fittings and Tubing
6
M
Easy Lock Manual Reset
1
Optional System Items:
P Pressure
Switch
I
Valve Visual Position Indicator
S
Valve Limit Switch
W Water
Motor
Alarm
Notes:
(
1) Shall be UL Listed in accordance with UL 258
(2) Shall be UL Listed in accordance with UL 393
(3) Shall be UL Listed in accordance with UL 753
(4) For 1½ & 2”: ¾” Drain Valve; 2½ & 3”: 1½” Drain Valve & 4” and larger: 2” Drain Valve
(5) Shall be UL Listed for fire protection service
(6) Construction material Brass/S.S 316 or corrosion resistant equivalent
(7) Items marked by 'B' standard Trim components provided in the trim package
(8) Items marked by 'A' are required trim components for the proper installation and use of the
deluge valve and are not provided in the trim package. These items must be obtained from
Bermad or an outside supplier prior to installation.
(9) Manual Emergency Release may be Model B (open Bracket shown) or Model D (with box)
Содержание 400E-Y
Страница 1: ...1 400E Y Deluge Valve Bermad 400E Y Torrent Deluge Valve Installation Operation Maintenance Manual IOM...
Страница 30: ...1 400E DP Y 400E DP Y Torrent Dry Pipe Valve Installation Operation Maintenance Manual IOM...
Страница 34: ...5 400E DP Y 3 1 1 Model 400E DP trim illustration Dry Pipe Valve...
Страница 38: ...1 400E Y Pre Action 400E Y Torrent Pre Action Systems Installation Operation Maintenance Manual IOM...
Страница 70: ...IOM Model 43T Pressure Relief Valve PAGE 9 OF 10 Figure 3B GA Drawing for Size 8 10...