5.7.6 Display indications
If configuring the device for use as floor temperature controller, only the time indication is active. If the
device has not been configured for use as floor temperature controller, the operator can select between
the following indications:
1. Time
2. Temperature
3. Time & temperature (alternating)
Factory setting: Time & temperature (alternating)
6. Experts menu
Depressing the right touch key and keeping it depressed for 10 seconds after accessing the “settings”
submenu (see 5.) from the main menu, enables to call the experts menu.
Caution!
This menu enables to make control settings that may only be performed by a qualified heating
specialist or an expert electrician. The settings made while operating in this mode cannot be reset via
the reset function and have to be made knowingly, therefore.
The following settings are available:
6.1 Controller type
The following controller configuration variants can be selected: “Room temperature controller”, (Room),
“Room temperature controller with floor temperature controller function” (Room&Floor) or “Floor tem-
perature controller” (Floor).
6.2 Language
The operator can select between the following languages: German, English, French, Dutch, Polish and
Russian.
6.3 Measuring correction
The measured temperature value can, in dependence on the related configuration, be adjusted with
regard to each individual sensor within a range from -5 K to +5K at 0.1K steps. At the same time, the
uncorrected value measured by the related sensor is being indicated on the display (factory setting 0.0).
6.4 Reset
Actuating this function resets all settings made outside of the experts menu (except for time and date)
to the condition as delivered.
6.5 Maximum temperature
(setting possible only when using the device as room temperature controller with floor temperature
controller function or as floor temperature controller) The maximum temperature measured by the floor
temperature can be defined within a range from 15 to 42°C. Damages to the floor in consequence of
excessive temperatures can thus be prevented (factory setting 42°C).