Alarm 2025 upon startup

This is a normal alarm, and occurs whenever motor data
is changed. The alarm shows for about 15 seconds while
the drive performs a motor calibration.

Fault 14 External Fault 1

External fault 1 is triggered when the VFD’s output fre-
quency exceeds motor nameplate frequency for more
than 10 seconds. Parameter 1404 controls the time delay
for this fault. If the system includes a large tank, or
requires more time to reach the setpoint, increase param-
eter 1404 as needed.

This fault is designed to protect against loss of prime,
broken shafts, etc. To disable this fault, adjust parameter
2002 Maximum speed, to the motor nameplate rpm.

Sleep

The BERKELEY VFD monitors pump speed to determine
demand. The pump is shut off when the rpm goes below
parameter 4023: PID Sleep Level. Always set parameter
4023 high enough to trigger sleep mode during low
demand conditions. Note that the shut-off head at param-
eter 4023: RPM, must be higher than the pressure set-
point. The PID sleep level can be determined by slowly
closing the discharge valve to confirm that the RPM
decreases to a level that triggers the sleep mode. The
PID sleep level can also be found by using the BEC2 pro-
gram, or see www.bec2.net.

Systems that use small tanks, or have a flat performance
curve, may cycle rapidly at intermediate flows. Correct
this by increasing Parameter 4024: PID Sleep Delay.

Caution: Do NOT increase parameter 4024 to a level that
will allow the pump to run with zero flow (dead head). The
water in the pump can overheat.

Sleep Options

Other devices such as flow or float switches can be used
to trigger sleep mode. Parameter 4022 determines the
method to trigger sleep mode. These options can be used
for pump up, pump down, and other on/off applications.

Multiple Systems / Setpoints

The BERKELEY VFD includes (2) independent process
control sets (groups 40 and 41). Group 41 parameters
can be selected using Digital Input (DI4). When first set-
up, groups 40 and 41 are identical. A set can be changed
later with parameters for a second process.

Constant Flow

After running the 

BERKELEY Assistant, the drive can be

configured for constant flow by adjusting parameters
4006: Units, and 4009: 100% Value.

Constant Flow Example 1:

Using a 4-20ma velocity meter with a range of 0 to 10
ft/sec. We want the display to be ft/sec.
Set 4006 to ft/sec
Set 4009 to 10   

Constant Flow Example 2:

Same setup as example 1, but we have a 4" pipe and
want the display to be gpm.
Set 4006 to gpm
Set 4009 to 393 (this is the flow in a 4" pipe which results
in a 10 ft/sec velocity).

Constant Flow Example 3:

Using a 4-20ma flow meter with a range of 0 to 100 gpm.
We want the display to be gpm.
Set 4006 to gpm
Set 4009 to 100 

Single Phase Connection

The BERKELEY VFD can operate on single phase input
power with a 50% de-rating. Power is connected to U1
and W1. The neutral / ground lead must be connected to
the drive terminal PE. Note that the current in the input
lines will be higher than the current to the motor. Use
fuses rated as shown in the users manual regardless of
phase.

Saving and Recalling Settings

The BERKELEY VFD can save and recall (2) sets of user
parameters (use parameter 9902). After running the
BERKELEY Assistant, and making changes, we recom-
mend the parameter set be saved. The parameter set can
then be recalled if parameters get accidentally changed.

Pass Code

The BERKELEY VFD can be pass code protected. Pass
coding is enabled by parameter 1602. The pass code is
entered in parameter 1603.

Submersible Motor Application

Submersible pump motors often have higher current draw
than an equivalent above ground motor. Submersible
motor size is usually based upon service factor amps
(which is higher than full amps).

HELPFUL HINTS

6

Содержание BPC Series

Страница 1: ...power lead should be attached to terminal 10 or the terminals as shown below and the 4 20 ma output lead should be attached to ter minal 5 Figure 3 The transducer has a brown power lead and a blue 4 20 ma output lead All jumper terminals may need to be loosened to attach leads above the jumper board The jumper board eliminates the need to hand wire termi nals 9 to 11 10 to 19 11 to 12 and 18 to 21...

Страница 2: ...speed and press SAVE The sample here shows 3450 RPM 6 EXIT EXIT 00 00 00 00 SAVE SAVE REM REM PAR EDIT PAR EDIT 3450 rpm 3450 rpm 9908 MOTOR NOM SPEED 9908 MOTOR NOM SPEED range 0 10 bar 145 psi max pressure 25 bar 362 5 psi UE 80 330 VDC OUT 4 20mA Load N 8V 0 02A Use this Full Range Value Do NOT use Maximum Pressure TRANSDUCER 100 VALUE Enter the transducer s full range value which should be sta...

Страница 3: ...r speed setting If the motor speed falls below this RPM the PID sleep function will be enabled This is a controller assigned value For additional informa tion refer to the ACS550 Users Manual Scroll to select the speed and then press SAVE The sample here shows 0 RPM waiting to be set Burn Hazard If the sleep level is set too low the pump my run without flow This can boil water inside the pump caus...

Страница 4: ...SEL 19 Internal 4011 INTERNAL SETPOINT USER DEFINED 4016 ACT1 INPUT 1 AI2 4017 ACT2 INPUT 1 AI2 4022 SLEEP SELECTION 7 INT 4024 PID SLEEP DELAY 10 SEC 4027 PID 1 PARAM SET 3 DI3 4102 INTEGRATION TIME 1 0S 4106 UNIT 25 PSI 4109 100 VALUE per 4009 4110 SET POINT SEL 19 INTERNAL 4111 INTERNAL SETPOINT per 4011 4122 SLEEP SELECTION 7 INT 4123 PID SLEEP LEVEL per 4023 4124 PID SLEEP DELAY 10 SEC 4125 W...

Страница 5: ...ve to restart For example if the set point is 60 PSI and the Wake Up Deviation is 10 PSI the drive will restart at 50 PSI Timer Function The BERKELEY VFD includes four timer functions Each timer function can include up to four daily weekly start and stop times The following example show the parameter changes required to use PID Set 2 on Monday Wednesday and Friday from 8 00 AM to 10 00 AM Paramete...

Страница 6: ...ns Multiple Systems Setpoints The BERKELEY VFD includes 2 independent process control sets groups 40 and 41 Group 41 parameters can be selected using Digital Input DI4 When first set up groups 40 and 41 are identical A set can be changed later with parameters for a second process Constant Flow After running the BERKELEY Assistant the drive can be configured for constant flow by adjusting parameter...

Страница 7: ...unexpected starts may cause damage or injury HELPFUL HINTS Continued Record setup values here Drive Model Drive Description Pump Model Pump Description Motor Model Motor Nominal Voltage Motor Nominal Current Motor Nominal Frequency Motor Nominal Speed Motor Nominal Power Minimum Speed required for submersibles Pressure Setpoint Transducer Full value Sleep Level Wake Up Deviation INSTALLATION RECOR...

Страница 8: ... under 86 F with proper flow conditions cooling the motor parameter 3007 can be set to 112 Submersible motors should always operate within its service factor limit Program Change Set Parameter 3007 to the percentage the motor is operating into service factor Use of Output Reactors and Filters The Load Reactor or KDR dampens voltage spikes on the PWM Pulse Width Modulated wave from the AC drive to ...

Отзывы: