Berkeley BPC Series Скачать руководство пользователя страница 5

9905 Motor Nom Voltage:

This is the nominal voltage

stated on the motor nameplate. If the motor is rated for
operation at multiple voltages, select the voltage nearest
the utility voltage. Ensure the motor connections corre-
spond to the voltage selected.

9906 Motor Nom Current:

This is the nominal current

found on the motor nameplate. Do not use service factor
amps.

9907 Motor Nom Freq:

This is the nominal frequency

found on the motor nameplate.

9908 Motor Nominal Speed:

This is the nominal speed

found on the motor nameplate. Use the number on the
motor nameplate. Do not enter 3600, 1800, etc.

9909 Motor Nom Power:

This is the nominal horsepower

found on the motor nameplate. Do not include service
factor unless the service factor is greater than 1.15.

2001 Min Speed (Required for Subs only):

This is the

minimum speed the motor is allowed to run. This mini-
mum is set to prevent damage to the motor thrust bear-
ings. Refer to motor literature to determine setting.

4011 Internal Setpoint:

This is the pressure the system

will maintain.

4009 100% Value:

This is the full scale reading of the

transducer. Ie. The 100% Value of a 200PSI transducer is
200PSI.

4023 PID Sleep Level:

Operation below this rpm will

cause the drive to stop.

4025 Wake-Up Dev:

This is the pressure drop that will

trigger the drive to restart. For example, if the set point is
60 PSI and the Wake-Up Deviation is 10 PSI, the drive
will restart at 50 PSI.

Timer Function:

The BERKELEY VFD includes four timer functions. Each
timer function can include up to four  daily / weekly start
and stop times.

The following example show the parameter changes
required to use PID Set 2 on Monday, Wednesday, and
Friday from 8:00 AM to 10:00 AM.

Parameter

Setting

3601 – Timers Enable  ................7 – Enabled
3602 – Start Time 1  .................. 8:00 AM
3603 – Stop Time 1 .................... 10:00 AM
3604 – Start Day 1  .................... 1-Monday
3605 – Stop Day 1  .................... 1-Monday
3606 – Start Time 2  .................. 8:00 AM
3607 – Stop Time 2 .................... 10:00 AM
3608 – Start Day 2 ...................... 3-Wednesday
3609 – Stop Day 2  .................... 3 – Wednesday
3610 – Start Time 3  .................. 8:00 AM
3611 – Stop Time 3 .................... 10:00 AM
3612 – Start Day 3  .................... 5-Friday
3612 – Stop Day 3  .................... 5-Friday
3626 – Timer Func1SCR  .......... 7 = P3 +P2 + P1
4027 – PID 1 Param Set  ............ 8 = Timer Function 1

DESCRIPTION OF INFORMATION REQUIRED

BY THE 

BERKELEY ASSISTANT

These instructions are only for systems that require tanks. Pressure tanks are generally required to maintain system pressure
during periods of low or no demand. Tank precharge must be less than the pressure set point – wake up deviation.

The tank can be sized using Boyle’s law (V1 x P1 = V2 x P2). Units are in gallons and PSI.

Drawdown =

Total Tank Size x (Pr14.7)

Total Tank Size x (Pr14.7)

(Se 14.7 – Wake Up Deviation)

(S14.7)

Typically tanks are sized for approximately 20% of pump capacity. For example, a 150 gpm pump typically requires 30
gallon total tank size.

TANK SIZING

__

5

Содержание BPC Series

Страница 1: ...power lead should be attached to terminal 10 or the terminals as shown below and the 4 20 ma output lead should be attached to ter minal 5 Figure 3 The transducer has a brown power lead and a blue 4 20 ma output lead All jumper terminals may need to be loosened to attach leads above the jumper board The jumper board eliminates the need to hand wire termi nals 9 to 11 10 to 19 11 to 12 and 18 to 21...

Страница 2: ...speed and press SAVE The sample here shows 3450 RPM 6 EXIT EXIT 00 00 00 00 SAVE SAVE REM REM PAR EDIT PAR EDIT 3450 rpm 3450 rpm 9908 MOTOR NOM SPEED 9908 MOTOR NOM SPEED range 0 10 bar 145 psi max pressure 25 bar 362 5 psi UE 80 330 VDC OUT 4 20mA Load N 8V 0 02A Use this Full Range Value Do NOT use Maximum Pressure TRANSDUCER 100 VALUE Enter the transducer s full range value which should be sta...

Страница 3: ...r speed setting If the motor speed falls below this RPM the PID sleep function will be enabled This is a controller assigned value For additional informa tion refer to the ACS550 Users Manual Scroll to select the speed and then press SAVE The sample here shows 0 RPM waiting to be set Burn Hazard If the sleep level is set too low the pump my run without flow This can boil water inside the pump caus...

Страница 4: ...SEL 19 Internal 4011 INTERNAL SETPOINT USER DEFINED 4016 ACT1 INPUT 1 AI2 4017 ACT2 INPUT 1 AI2 4022 SLEEP SELECTION 7 INT 4024 PID SLEEP DELAY 10 SEC 4027 PID 1 PARAM SET 3 DI3 4102 INTEGRATION TIME 1 0S 4106 UNIT 25 PSI 4109 100 VALUE per 4009 4110 SET POINT SEL 19 INTERNAL 4111 INTERNAL SETPOINT per 4011 4122 SLEEP SELECTION 7 INT 4123 PID SLEEP LEVEL per 4023 4124 PID SLEEP DELAY 10 SEC 4125 W...

Страница 5: ...ve to restart For example if the set point is 60 PSI and the Wake Up Deviation is 10 PSI the drive will restart at 50 PSI Timer Function The BERKELEY VFD includes four timer functions Each timer function can include up to four daily weekly start and stop times The following example show the parameter changes required to use PID Set 2 on Monday Wednesday and Friday from 8 00 AM to 10 00 AM Paramete...

Страница 6: ...ns Multiple Systems Setpoints The BERKELEY VFD includes 2 independent process control sets groups 40 and 41 Group 41 parameters can be selected using Digital Input DI4 When first set up groups 40 and 41 are identical A set can be changed later with parameters for a second process Constant Flow After running the BERKELEY Assistant the drive can be configured for constant flow by adjusting parameter...

Страница 7: ...unexpected starts may cause damage or injury HELPFUL HINTS Continued Record setup values here Drive Model Drive Description Pump Model Pump Description Motor Model Motor Nominal Voltage Motor Nominal Current Motor Nominal Frequency Motor Nominal Speed Motor Nominal Power Minimum Speed required for submersibles Pressure Setpoint Transducer Full value Sleep Level Wake Up Deviation INSTALLATION RECOR...

Страница 8: ... under 86 F with proper flow conditions cooling the motor parameter 3007 can be set to 112 Submersible motors should always operate within its service factor limit Program Change Set Parameter 3007 to the percentage the motor is operating into service factor Use of Output Reactors and Filters The Load Reactor or KDR dampens voltage spikes on the PWM Pulse Width Modulated wave from the AC drive to ...

Отзывы: