![BERGHOF B-PRIMIS DC-PRIME DC2110W X CM Скачать руководство пользователя страница 44](http://html.mh-extra.com/html/berghof/b-primis-dc-prime-dc2110w-x-cm/b-primis-dc-prime-dc2110w-x-cm_user-handbook-manual_2737010044.webp)
USER HANDBOOK 1.2 | B-PRIMIS DC/ET PRIME 2110W X C, 2115WUX C
Berghof Automation GmbH | Harretstraße 1 | 72800 Eningen |
www.berghof-automation.com
270011X00_B-PRIMIS_ET-DC-PRIME 2110W-2115W_EN.docx
44
5.2.7. EtherCAT (DC2115WUX CM / DC2110W X CM)
The onboard Ethernet adapter has two RJ-45 10/100 Base-T interfaces for networking. The Ethernet
interface X6 can be used as the EtherCAT master.
Fig. 26: EtherCAT interface X6
Assignment of EtherCAT interface connector X6
Pin Assignment
Pin
Assignment
1
TX+
5
NC
2
TX
–
6
RX
–
3
RX+
7
NC
4
NC
8
NC
LEDs
LED
Colour
Meaning to IEEE 802.3 clause 25
LNK/RCV
green
Link, Data Receive
Flashing: connection active; data transfer in pro-
gress
Off: no connection established
SPEED
yellow
On = 100 Mbit/s
Off = 10 Mbit/s