24
2 4 Handling
A transpallet or forklift must be used for handling.
A transpallet or forklift must be used for handling.
A transpallet or forklift must be used for handling.
- place two wooden boards (1) near the pallet (2)
- slide the modular system above the wooden boards
- adjust the feet (3) of the modular system until they
rest on the ground
- slide the wooden boards out.
3
3
2
1
b
The packaging material must be disposed of care-
fully and must not be abandoned, as it is a source of
potential danger.
2 5 Installation premises
The
Power Plus Box
systems (models
EXT
) are designed
for outdoor installation. In the case of installation indoors
(models
INT
), they are B23 category devices and must be
installed in permanently ventilated rooms in compliance
with the currently applicable Technical Regulation. In this
case, a suitable system must be prepared for collecting
condensate and for flue gas exhaust (see the specific
chapter "Flue gas evacuation for installations in central
heating plants”).
b
Take into consideration the space that is required in
order to access the safety and control devices and
to perform the maintenance operations. If possible,
maintain a distance of approx. 1 metre between the
rear panel and the wall. Note that the front doors can
be removed easily.
b
Check that the appliance's electrical protection level
is suitable for the place of installation.
≥ 1 m
≥ 1 m
≥ 1 m
≥ 1 m
1250
1530
650
2 6 Installation in older systems and
systems requiring modernisation
If the system is being installed in an old or refurbished sys-
tem, check that:
- If installing in a central heating plant, the flue is suit-
able for the condensing equipment, at the tempera-
tures of the products of combustion, calculated and
built according to standard. it is as straight as pos-
sible, air-tight, isolated and not have obstructions or
constrictions
- Make sure that the flue is fitted with a condensation
drainage union