Beretta NOVELLA 24-31 RAI PV Скачать руководство пользователя страница 14

INST

ALLA

TION 

MANUAL

14

3  INSTALLATION

3.1   

Installation standards

The boiler must be only be installed by qua-
lified personnel in conformity to the following 
reference standards: 

 - UNI-CIG 7129 
 - UNI-CIG 7131 
 - IEC 64-8. 

Installers must also ensure conformity to fire 
prevention standards, gas safety standards 
and local bylaws. 

3.2   

Place of installation

Novella RAI

 boilers must be installed in 

rooms with vents that conform to applicable 
technical standards and safety legislation. 

 

a

Boilers must be installed indoors. They 
are not designed for outdoor use and 
are not fitted with automatic frost protec-
tion devices. 

IMPORTANT

Before  installing  the  boiler,  thoroughly  flush 
out all pipes to remove any dirt and deposits 
that could compromise the correct functioning 
of the boiler.
Install a water collector under the safety valve 
and connect it to the nearest drain to evacua-
te any water coming out of the safety in the 
event of overpressure. The domestic hot water 
circuit does not require a safety valve but the 
installer  should  nevertheless  check  that  the 
water supply pressure does not exceed 6 bar. 
If necessary, install a pressure reducer. 

Before lighting the burner for the first time, 

make sure that the boiler is configured for 

use with the type of gas supplied. The type 

of gas is specified on the packaging label 

and on the boiler’s own name plate. 

Make  sure  that  the  flue  is  able  to  withstand 
the temperature of the flue gases and that it 
has been designed and made in conformity to 
applicable standards. The flue must also be as 
straight as possible, sealed, insulated and not 
blocked or choked. 

3.3   

Installation in existing systems

Perform the following checks before installing 
Novella boilers in existing systems. 

 - Check  that  the  flue  is  large  enough  and 

suitable for the characteristics of the boiler. 

 - Check that the characteristics of the boiler’s 

pump (see the graph on page 12) are suita-
ble for the existing system. Existing pumps 
are no longer needed. 

 - Make  sure  that  the  central  heating  circuit 

has been flushed out to remove all sludge 
and limescale, and that it has been properly 
de-aerated. 

 - Make  sure  that  the  system  is  fitted  with 

safety and control devices that conform to 
applicable legislation and standards. 

 - Check  the  hardness  of  the  water  supply 

to ascertain whether a softening system is 
required. 

Refer to the following values. 

REFERENCE VALUES 

pH

6-8

Electrical conductivity  less than 200 mV/cm (25°C) 
Chlorine ions 

less than 50 ppm 

Sulphuric acid ions 

less than 50 ppm 

Total iron 

less than 0,3 ppm 

Alkalinity M 

less than 50 ppm 

Total hardness 

35° F 

Sulphur ions 

none 

Ammonia ions 

none 

Silicon ions 

less than 30 ppm 

Содержание NOVELLA 24-31 RAI PV

Страница 1: ...NOVELLA 24 31 45 RAI 24 31 RAI PV BOILERS CAST IRON BASE INSTALLATION MANUAL...

Страница 2: ...ation a STOP Identifies actions that you MUST NOT do Novella boilers conform to the basic requirements of the following directives Gas Appliances Directive 2009 142 CE Boiler Efficiency Directive 92 4...

Страница 3: ...Wiring diagram 13 3 INSTALLATION 14 3 1 Installation standards 14 3 2 Place of installation 14 3 3 Installation in existing systems 14 3 4 Water connections 15 3 5 Electrical connections 15 3 6 Gas c...

Страница 4: ...onnel If the boiler is not going to be used for an extended period of time contact the manufacturer s Technical Assistance Service to have at least the following ope rations performed Switch the boile...

Страница 5: ...ating system i e when the room thermostat trips Novella boilers can be connected to a storage cylinder to produce domestic hot water and can be equipped with temperature controllers in the form of spe...

Страница 6: ...etection unit 5 CH pump 6 Water circuit drain cock 7 Ignition electrode 8 Flame detection sensor 9 Burner 10 Gas supply solenoid valve 11 Lifting points 12 Expansion vessel Novella 24 31 45 RAI boiler...

Страница 7: ...26660 38700 Electrical consumption W 103 15 103 15 Boiler class II 2H3 Power supply voltage V Hz 230 50 Index of protection IP 40 Losses from stack and casing with burner off 1 65 1 37 1 23 Central h...

Страница 8: ...sure mwp Maximum admissible temperature Power supply Maximum current draw NOx class Maximum energy consumption Gas supply pressure CLASS OF BOILER TYPE OF BOILER COUNTRY OF DESTINATION Index of protec...

Страница 9: ...the manuals and keep them safe Fig 2 6 MODEL 24 RAI 24 RAI PV 31 RAI 31 RAI PV 45 RAI Net weight 100 108 118 126 154 kg Gross weight 119 127 138 146 174 kg 2 8 Handling Once you have removed the pack...

Страница 10: ...L 10 2 9 Overall dimensions and water fittings Fig 2 8 Fig 2 9 Novella 24 31 45 RAI boilers Novella 24 31 RAI PV boilers DESCRIPTION MODEL 24 RAI 24 RAI PV 31 RAI 31 RAI PV 45 RAI A 450 154 mm B 675 7...

Страница 11: ...F Water circuit temperature gauge sensor A Water circuit drain cock B CH circuit temperature control sensor C Water circuit temperature gauge sensor D Safety thermostat temperature sensor G Safety th...

Страница 12: ...ilers are pre fitted with a pump to which all water and electrical connections have already been made Pump performance is illustrated by the curves in the following graph the right size bear in mind t...

Страница 13: ...er lockout LED warning light RS Burner reset button TR CH circuit temperature control TS Safety thermostat manual reset TF Flue gas thermostat manual reset Fig 2 15 PI CH pump AP Ignition and flame de...

Страница 14: ...configured for use with the type of gas supplied The type of gas is specified on the packaging label and on the boiler s own name plate Make sure that the flue is able to withstand the temperature of...

Страница 15: ...I 31 RAI 45 RAI A 64 28 28 mm Novella 24 31 45 RAI Novella 24 31 RAI PV 3 5 Electrical connections Use a multi pole disconnector with a contact gap of at least 3 mm to connect the appliance to the mai...

Страница 16: ...derneath fig 3 3 Connect up the optional room thermostat and or timer as shown in the electrical wiring diagrams in this manual Connect up the electrical power supply fig 3 4 Connect up the room therm...

Страница 17: ...pplicable legisla tion and standards b b On completion of the installation check that all joints are sealed in conformity to the relevant installation standards 3 7 Gas supply conversion The boiler co...

Страница 18: ...ow fig 3 11 24 RAI 31 RAI 45 RAI G30 G31 G30 G31 G30 G31 28 4 36 5 28 8 34 7 27 8 35 7 mbar Disconnect the pressure gauge and close the pressure measurement point Check the tightness of all the joints...

Страница 19: ...he boi ler immediately in the event of flue gas blowback b b Uninsulated flue pipes are potentially dangerous and can cause burns Fig 3 13 DESCRIPTION MODEL 24 RAI 31 RAI 45 RAI B 72 77 97 mm I 132 14...

Страница 20: ...tching the boiler s mains power switch and con trol panel switch OFF 0 before starting to empty the boiler fig 3 17 Make sure that the water circuit shut off cocks are closed Connect a rubber hose to...

Страница 21: ...mer or timer thermostat make sure that this is switched On and adjusted to the required temperature 20 C fig 4 2 Adjust the boiler s own temperature control to the desired temperature not necessary if...

Страница 22: ...llows to reset the safety ther mostat Wait for about 1 minute then press the bur ner reset button fig 4 6 Wait for the burner to complete the entire start up cycle again up to the ignition of the flam...

Страница 23: ...mperature control is turned down fig 4 8 The control panel switch is switched OFF fig 4 8 The temperature setting on the room ther mostat or timer is reduced fig 4 9 Make sure that the pump if fitted...

Страница 24: ...following operations Switch the boiler off at the control panel switch and check that the green power indi cator goes out fig 5 1 Turn the mains power switch OFF fig 5 2 Close the boiler s fuel cock a...

Страница 25: ...normally consists of the following operations Remove encrustations from the burner Remove encrustations from the heat exchangers Check and clean the flue pipes Check the efficiency of the external cas...

Страница 26: ...ber 1100279 Pump or valve controlled multizone central hea ting kit with total shut down function fig 7 2 part number 696439 RO120 storage cylinder fig 7 3 part number 696339 Pump manifold fig 7 4 par...

Страница 27: ......

Страница 28: ...taclima it Beretta is constantly improving its products and therefore reserves the right to modify the characteristics and specifications of the appliance described in this manual at any time and with...

Отзывы: