ENGLISH
18
Mynute Green E C.S.I. - R.S.I.
19
DESCRIPTION
Mynute Green
E 25 C.S.I.
Mynute Green
E 30 C.S.I.
Mynute Green
E 20 R.S.I.
Mynute Green
E 30 R.S.I.
Heating
Heat input
kW
20,00
25,00
20,00
25,00
kcal/h
17.200
21.500
17.200
21.500
Maximum heat output (80/60°C)
kW
19,64
24,48
19,62
24,48
kcal/h
16.890
21.049
16.873
21.049
Maximum heat output (50/30°C)
kW
21,14
26,50
21,44
26,50
kcal/h
18.180
22.790
18.438
22.790
Minimum heat input
kW
6,00
6,00
2,80 (
G31
: 4,00)
6,00
kcal/h
5.160
5.160
2.408 (
G31
: 3.440)
5.160
Minimum heat output (80/60°C)
kW
5,87
5,87
2,76 (
G31
: 3,95)
5,87
kcal/h
5.052
5.052
2.377 (
G31
: 3.399)
5.052
Minimum heat output (50/30°C)
kW
6,44
6,44
3,00 (
G31
: 4,20)
6,44
kcal/h
5.160
5.537
2.577 (
G31
: 3.609)
5.537
Nominal Range Rated heat output (Qn)
kW
-
-
20,00
-
kcal/h
-
-
17.200
-
Minimum Range Rated heat output (Qm)
kW
-
-
6,00 (
G31
: 6,00)
-
kcal/h
-
-
5.160 (
G31
: 5.160)
-
DHW
Heat input
kW
25,00
30,00
20,00
30,00
kcal/h
21.500
25.800
17.200
25.800
Maximum heat output (*)
kW
25,00
30,00
20,00
30,00
kcal/h
21.500
25.800
17.200
25.800
Minimum heat input
kW
6,00
6,00
2,80 (
G31
: 4,00)
6,00
kcal/h
5.160
5.160
2.408 (
G31
: 3.440)
5.160
Minimum heat output (*)
kW
6,00
6,00
2,80 (
G31
: 4,00)
6,00
kcal/h
5.160
5.160
2.408 (
G31
: 3.440)
5.160
(*) average value of various DHW operating conditions
Useful efficiency Pn max - Pn min (80°/60°)
%
98,2 - 97,9
97,9 - 97,9
98,1 - 98,7
97,9 - 97,9
Useful efficiency 30%
(47° return)
%
103,4
103,5
-
103,5
Combustion performance
%
98,5
98,2
98,3
98,2
Useful efficiency Pn max - Pn min (50°/30°)
%
105,7 - 107,3
106,0 - 107,3
107,2 - 107,0
106,0 - 107,3
Useful efficiency 30% (30° return)
%
109,6
109,6
109,6
109,6
Average Range Rated efficiency P (80°/60°)
%
-
-
98,4
-
Electric power (max power CH)
W
79
88
81
88
Electric power (max power DHW)
W
88
102
81
102
Circulator electric power (1.000 l/h)
W
51
51
51
51
Category
II2H3P
II2H3P
II2H3P
II2H3P
Country of destination
(+)
(+)
(+)
(+)
Power supply voltage
V - Hz
230 - 50
230 - 50
230 - 50
230 - 50
Degree of Protection
IP
X5D
X5D
X5D
X5D
Pressure drops on flue with burner on
%
1,48
1,81
1,68
1,81
Pressure drops on flue with burner off
%
0,14
0,11
0,05
0,11
Heating operation
Pressure - maximum temperature
bar - °C
3 - 90
3 - 90
3 - 90
3 - 90
Minimum pressure for standard operation
bar
0,25 - 0,45
0,25 - 0,45
0,25 - 0,45
0,25 - 0,45
Selection field of heating water temperature
°C
20/45 - 40/80
20/45 - 40/80
20/45 - 40/80
20/45 - 40/80
Pump: maximum head available
mbar
326
326
326
326
for system capacity
l/h
1.000
1.000
1.000
1.000
Membrane expansion tank
l
8
9
8
9
Expansion tank pre-charge
bar
1
1
1
1
DHW operation
Maximum pressure
bar
6
6
-
-
Minimum pressure
bar
0,2
0,2
-
-
Hot water quantity with ∆t 25°C
l/min
14,3
17,2
-
-
with ∆t 30°C
l/min
11,9
14,3
-
-
with ∆t 35°C
l/min
10,2
12,3
-
-
DHW minimum output
l/min
2
2
-
-
Selection field of DHW temperature
°C
37 - 60
37 - 60
-
-
Flow regulator
l/min
11
13
-
-