background image

INST

ALLA

TION MANUAL

6

Product description

Identification

IDRA DS

,

 

solar storage cylinders are double coil units 

of 300, 400, 500, 1000, 1500, 2000 and 3000 litres in 
capacity, and are specifically designed for integration in 
domestic hot water production systems heated by 

SC-B 

06

 solar collectors.

The most important technical features of these storage 

cylinders are:

-  The cylinder and coils are specially designed and sha-

ped for optimum performance in terms of stratification, 
heat exchange and replenishment times. 

- The cylinder lining is bacteriologically inert for maxi-

mum hygiene, reduced lime scale deposits and easy 
cleaning.

-  Water fittings are available at different heights, permit-

ting different hot water generators to be used without 
reducing stratification effect.

-  CFC-free polyurethane insulation and an elegant exter-

nal coating reduce heat loss and improve efficiency.

- A flange is provided for easy cleaning and maintenan-

ce and a magnesium anode is provided to prevent 
corrosion.

IDRA DS 

storage cylinders can be connected to a 

special solar controller and can be integrated in solar 
heating systems in which boilers or water heaters serve 
as auxiliary heat generators.

IDRA DS 

solar storage cylinders are identified by two plates:

If these plates or any other means of clearly identifying the product are defaced, 
removed or lost, proper installation and servicing may be rendered difficult.

– Data plate

   

 

 

  This lists the technical specifications and performance of the product.

– Product identification plate

   

This bears the name of the product.

– Serial number plate

  

 

 

This states the serial number, model, absor-
bed power and capacity.

Beretta Caldaie
Via Risorgimento, 13
23900 Lecco (LC)

Code

bar

V-Hz

l

Obligatory ground connection

W

kW

l/1'

kW

l/1'

SOLAR STORAGE CYLINDER

Model

Serial
number

Year

Maximum absorbed power [Primary T = 80°C]

Specific top flow rate [∆T 35°C]

Bottom maximum power consumption [Primary T = 80°C]

Specific bottom flow rate  [∆T 35°C]

Maximum working pressure of cylinder

Storage cylinder capacity

Electrical consumption

Power supply

Beretta Caldaie
Via Risorgimento, 13
23900 Lecco (LC)

Serial number

kW

kW

Maximum
absorbed power

Model

Bottom max.
power consumption 

Содержание IDRA N DS 1500

Страница 1: ...STORAGE CYLINDER IDRA DS SOLAR INSTALLATION MANUAL...

Страница 2: ...INSTALLATION MANUAL 2 Range MODEL CODE IDRA DS 300 1150409 IDRA DS 400 1150419 IDRA DS 500 1150429 IDRA DS 1000 20001400 IDRA DS 1500 20002597 IDRA DS 2000 20002598 IDRA DS 3000 20002599...

Страница 3: ...n authorised Beretta Technical Assistance Centre Their personnel are specially trained to keep your storage cylinder efficient and cheap to run Technical Assistance Centres also stock any original spa...

Страница 4: ...tems requiring modernisation 16 Water connections 17 Location of probes 21 TECHNICAL ASSISTANCE Preparing for initial start up pag 21 Initial start up 21 Checks during and after initial start up 22 Pr...

Страница 5: ...ailable separa tely and must be mixed with water in a percentage varying from 30 to 50 as instructed in the rele vant installation and maintenance manual bOnly fill the solar heating system with water...

Страница 6: ...n IDRA DS storage cylinders can be connected to a special solar controller and can be integrated in solar heating systems in which boilers or water heaters serve as auxiliary heat generators IDRA DS s...

Страница 7: ...ontroller probe well 5 Cylinder inspection flange 6 Flange cover 7 Bottom coil 8 Polyurethane insulation 9 Top coil 10 Cylinder 11 Second magnesium anode only for IDRA DS 1000 1500 2000 and 3000 12 Sl...

Страница 8: ...ge cylinder capacity 300 400 500 888 1450 2054 2959 l External diameter 653 755 755 990 1200 1300 1450 mm Height 1542 1535 1800 2050 2120 2405 2665 mm Insulation thickness 51 5 100 mm First magnesium...

Страница 9: ...the installation and maintenance manual for the solar heating system A second anode for the inspection flange is supplied as standard on model IDRA DS 1000 and 1500 but must be fitted by the installer...

Страница 10: ...25 100 75 50 25 0 IDRA DS 300 IDRA DS 400 IDRA DS 500 0 0 25 0 5 0 75 1 1 25 1 5 PERDITE DI CARICO mbar PORTATA m3 h 60 55 50 45 40 35 30 25 20 15 10 5 0 IDRA DS 300 IDRA DS 500 IDRA DS 400 TOP COIL p...

Страница 11: ...RA DS 1500 IDRA DS 1000 IDRA DS 2000 IDRA DS 3000 0 1 2 3 4 6 PERDITA DI CARICO mbar PORTATA m3 h 3200 3000 2800 2600 2400 2200 2000 1800 1600 1400 1200 1000 800 600 400 200 0 5 IDRA DS 1000 IDRA DS 2...

Страница 12: ...ted by a plastic bag and supported on a wooden pallet The second package contains another plastic bag with the elegantly finished polyurethane insulation fitting sleeves for the insulation thermoforme...

Страница 13: ...DS 1000 1500 2000 and 3000 of the CONTROL BOX SUN 2 Dimensions and weight DESCRIPTION IDRA DS 300 400 500 1000 1500 2000 3000 H Height 1542 1535 1800 2050 2120 2405 2665 mm Diameter 653 755 755 990 1...

Страница 14: ...he insula tion at the hinges Models 300 400 500 1000 Models1500 IDRA DS 2000 and 3000 To lift storage cylinders first remove the insulation then attach a rope of adequate strength to the top of the cy...

Страница 15: ...carefully lining up the fittings with the holes on the insi de of the insulation Secure the insulation in place with the zips 4 at the edges of the two sections Perforate the insulation at the fitting...

Страница 16: ...ring modernisation always per form the following checks Make sure that the system is fitted with safety and control devices in accordance with applicable legislation and stan dards Make sure that the...

Страница 17: ...corresponding fixing system water control group expansion vessel and thermostatic mixer valve Water fittings have the following specifications We recommend that you install isolating valves in the out...

Страница 18: ...1 4 M 1 1 2 F MC Outlet from boiler 1 1 4 F RC Return to boiler 1 1 4 F M Collector outlet 1 1 4 F R Collector return 1 1 4 F RL DHW recirculation 1 F EAF SB Domestic cold water inlet storage cylinde...

Страница 19: ...rom boiler 1 1 2 F 1 1 4 F RC Return to boiler 1 1 2 F 1 1 4 F M Collector outlet 1 1 2 F 1 1 4 F R Collector return 1 1 2 F 1 1 4 F RL DHW recirculation 1 F EAF SB Domestic cold water inlet storage c...

Страница 20: ...able collection and drain system The manufacturer declines all responsibility for damage caused by water escaping from the safety valve bUse a thermostatic mixer valve 19 to limit the domestic hot wat...

Страница 21: ...r heating system have been made correctly The solar heating circuit has been correctly flushed out and filled with water glycol mix and all air has been bled out of the circuit Heat is only transferre...

Страница 22: ...area Check that the solar heating circuit has been properly bled Check that the cold pressure of the system is approxi mately 3 bar Check that the safety valve operates at 6 bar Check that all pipes...

Страница 23: ...der s valve group and to any associated boiler OFF at the main switch and at the control panel Close the shut off cocks for the domestic hot water circuit Drain the cylinder s secondary water circuit...

Страница 24: ...triethylene INTERNAL CLEANING Removing and checking the magnesium anode Remove the cap 1 cover 2 and the anode insulator disc Use a 45 mm wrench to unscrew the anode plug 3 Check the magnesium anode...

Страница 25: ...ough the access hole Once cleaned refit all components following the above steps in the reverse order bTighten the nuts 7 to secure the flange 8 pro ceeding diagonally around the flange to apply press...

Страница 26: ...h or too low Set a T of 8 10 C There is lime scale or sludge in the cylinder Check and clean as necessary The flow rate is too high Reduce pump speed and turn the flow rate adjustment screw on the val...

Страница 27: ......

Страница 28: ...stenza Tecnica Numero Unico 199 12 12 12 www berettaclima it The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment and accesso...