41
41
ENGLISH
PP1
PP2
PP3
PP1
LOW proportional head curve
PP2
AVERAGE proportional head curve
PP3
HIGH proportional head curve
Constant head
The circulation unit works at constant head, irrespective of the heat
request. The working point of the circulation unit will move along the
selected curve on the basis of the heat request.
CP1
CP2
CP3
CP1
LOW constant head curve
CP2
AVERAGE constant head curve
CP3
HIGH constant head curve
Constant curve
The circulation unit works at constant speed, irrespective of the heat
request from the system. The working point of the circulation unit will
move along the selected curve on the basis of the heat request.
C1
C2
C3
C4
C1
Curve 1 = 4 metres
C2
Curve 2 = 5 metres
C3
Curve 3 = 6 metres
C4
Curve 4 MAX = 7 metres
3.12 Parameter table
Description
U/M
Value
Power On mixing valve closing time
sec
140
Mixing valve closing time
sec
120
Post-circulation time
sec
30
Over delivery time
°C
55
Over delivery wait time
sec
120
Zone restore time
sec
120
Anti block timer
h
24
First anti-freeze threshold
°C
10
Second anti-freeze threshold
°C
6
Anti-freeze time
min
4
Zone 1 minimum temperature
°C
25
Zone 1 maximum temperature
°C
50
Zone 2 minimum temperature
°C
25
Zone 2 maximum temperature
°C
50
Zone 3 minimum temperature
°C
40
Zone 3 maximum temperature
°C
80
"Screed heater" function: Minimum T
°C
20
"Screed heater" function: Maximum T
°C
35
b
The parameters can only be set to different values by a qualified
technician and only if absolutely necessary.
b
The manufacturer declines all liability if parameter settings are
incorrect.
3.13 Alarm list
The following table shows the alarms of the
CONNECT LE
board which
are transmitted to the REC.
Alarm no.
Description
47
External sensor open or in short circuit
48
External sensor open or in short circuit in system ther-
moregulation mode
49
No communication between the main micro and the periph-
eral micro
84
Mix delivery sensor MIX1, channel 2 in short circuit
85
Mix delivery sensor MIX1, channel 2 interrupted
86
Mix delivery sensor MIX2, channel 3 in short circuit
87
Mix delivery sensor MIX2, channel 3 interrupted
88
Incorrect combination between CHANNEL and ZONE
89
Reading/writing error in eeprom on main micro
If the
CONNECT LE
is connected to the boiler in
Link mode
, the
CON-
NECT LE
board will, in real time, monitor the presence of any alarm
signals (code
B
) coming from the boiler board and will transmit
them to all the connected REC which will then display them. It is pos-
sible to reset the boiler alarms using the REC if the boiler board is
prearranged for this.
If the "sensor interrupted" alarm is signalled on the low temperature
zone, the corresponding circulation unit will be stopped and the mixing
valve will be completely closed for 120 seconds.
After this time, a post circulation will be activated for 120 seconds.
If the "sensor interrupted" alarm is restored, the adjustment cycle is
reactivated otherwise the zone will remain bocked until the operating
conditions are restored.
3.14 Checks after commissioning
Once commissioning has been completed, check:
-
the plumbing circuit for leaks
-
that the heating system is pressurised
-
that the main switch for the system works
-
that the electrical connections are correct.
For heat requests from a mixed system, check that the mixing valves
open and close correctly.
b
If even one of these checks provides a negative result, the sys-
tem is to be switched off and must not be started up again until
the fault has been eliminated.