NOTICE
Do not use heavy-duty anchors from other manufacturers or with different
specifications.
The heavy-duty anchors listed above can be used subject to the following struc-
tural requirements:
¡
Concrete strength class ≥ B 25
¡
Ceiling thickness ≥ 5,9 inch
¡
Edge distance D from the next ceiling opening ≥ 5,9 inch
Ceiling anchor plate Pitch circle Ø
Drilled hole Ø
HILTI heavy-duty
anchor
CB 5103304
10,62 inch
0,66 inch
HSL-G-TZ M10/20
(Type A)
Spacer
Pitch circle Ø
Drilled hole Ø
HILTI stud anchor
CB 1100104
10,62 inch
0,43 inch
HST M8/10
(Type B)
Type
d0
t
hs
l
Md
WAF
x
A
0,59
3,74
3,26
4,52
50
0,66
0,78
B
0,31
2,55
1,96
2,95
25
0,51
0,39
(All figures in inch, except Md: stated in Nm)
Abbrevi-
ation
Explanation
Abbrevia-
tion
Explanation
d0
Nominal drill-bit diameter Md
Tightening torque
t
Minimum bore-hole depth WAF
Width across flats
hs
Minimum embedding
depth
x
Attachment height
General structural
engineering conditions
Fig. 10: Edge distance
Heavy-duty anchors
used
Dimensional drawing and
dimensions
Examination light CHROMOPHARE F 300
Installation and initial start-up
34