Remark:

 

Deadzone for floor temp.: i.e. the setting deadzone for floor sensor is 2, 
OSV is 42

, when actual temp. reach 44

, the relay will stop working; 

when actual temp. is back to 40

, the relay starts working again. It works 

when room temp. is lower than set temp.

Sensor error:
Please select the right sensor mode. If select the different mode or there 
is error of sensor, Err will display on the LCD screen, the thermostat will 
stop heating till the problem is solved.

Display Code

Function

Setting And Options

Factory Defult

SEN

Sensor mode

0:Internal sensor
1:Floor sensor
2:Both internal sensor 
and floor sensor

0

OSV

Set temp. range 
for floor sensor

5-99

42

DIF

Deadzone 
for floor temp.

1-9

2

SVH

High limit temp. 
for internal sensor

5-99

35

SVL

Low limit temp. 
for internal sensor

5-99

5

ADJ

Measure temp.

Check and calibrate the 
actual room temp.

0.5

accuracy

calibrate

 

FRE

Anti-frozen

00

Close anti-frozen

01

Open anti-frozen

00

PON

Power memory

00

Power

 memory off

01

Power memory on

00

FAC

Factory setting

00

Return to factory 

setting
08

Just

 

display

08

6. Advanced Setting

In the state of power-off, long press and hold       then press     into advanced 
settingmode. Then press   

   

to set relative item.  

   

7. Mod-bus RTU communication protocol.

Standard Modbus RTU protocol, serial RS485 with two lines, communicate 
technical parameter : 

Baud rate 9600, 8 data bits, no parity data check ,  2 stop bits
Please keep Register command 03, write single register command 06.
1.Key-lock, power on off, register address 00:
   Key-lock (high byte), 0: unlock, 1:lock;
   Power switch: (low byte), 0: power off, 1: power on.

  

2.Room measure temperature , room set temperature, register address 01:
   Room measure temperature(high byte), data range :0-199, relative
   temperature : 0-99.5, at this byte “write” No valid;
   Room set temperature (low byte), data range :0-199, relative 
   temperature : 0-99.5, 

 

3.Period control mode, sensor set, register address 02:
   Period control mode ( high byte), data range : 0-3,
   0: manual control
   1.Monday~ Friday, 6 periods control, Saturday- Sunday is 2 periods control.
   2.Monday ~ Saturday, 6 periods control, Sunday is 2 periods control.
   3.Monday ~ Sunday 6 periods control,
     Sensor set (low byte), date range 0-2, 

0: room sensor control; 1. External floor sensor control 2: room sensor control , 
floor sensor limit floor temperature.

4.Floor temperature set, floor temperature control differential , register address03:
   Floor temperature set (high byte), data range 5-60,  relative floor temperature set 
   5-60 degree.
   Floor temperature control differential, data range 1-9, relative floor control 
   differential set 1-9degree.

5.Room max temperature set, room min temperature set, register address 04:
   Room max temperature set (high byte), data range : 5-99, relative temperature 
   5-99degree.
   Room min temperature set (low byte), data range : 5-99, relative temperature 
   5-99degree.

6.Room temperature adjustment, register address 05:
   Data range 0xFFF6~0x000A, relative temperature adjustment is -5~5degree.
   Temperature adjustment is the twice of actual temperature, that will be actual 
   adjustment 
   is 0.5degree, this is for the transmit for modbus communication , enlarged twice to
   integer format.

7.Anti-frozen set,  power state memory set, register address 06:
   Anti-frozen set ( high byte), 0: no anti-frozen function, 1: open Anti-frozen function.
   Power state memory set (low byte), 0: power off state after power recover. 
   1. Power on state after power recover.

8, Floor temperature measurement, register address 07:
    Floor temperature measurement (low byte), data range : 0-199, 
    relative temperature 0-99.5degree.

9, Time_ Hour, Time_Minute, register address 08:
    Hour (high byte), data range 0-23, 24 hours;
    Minute (low byte), data range 0-59.

10, Time_ second,  Time_week, register address 09:
     Second ( high byte), data range 0-59;
     Week ( low byte), data range 1-7.

11, Period 1_hour, Period 1_minute, register address 10:
      Hour (high byte), data range 0-23, 24 hours.
      Minute (low byte), data range 0-59.

12, Period 2_hour, Period 2_minute, register address 11:
       Same as 11.
13

Period 3_hour, Period 3_minute, register address 12:

       Same as 11.

14, Period 4_hour, Period 4_minute, register address 13:
      Same as 11.

15, Period 5_hour, Period 5_minute, register address 14:
      Same as 11.

16, Period 6_hour, Period 6_minute, register address 15:
      Same as 11.

17, Period 7_hour, Period 7_minute, register address 16:
      Same as 11.

18, Period 8_hour, Period 8_minute, register address 17:
      Same as 11.

19, Period 1_room temperature, Period 2_room temperature, register 
      address 18:
      Period 1_room temperature ( high byte), data range 0-199, relative 
      temperature 0-99.5degree.
      Period 2_room temperature ( low byte), data range 0-199, relative 
      temperature 0-99.5degree.

20, Period 3_room temperature, Period 4_room temperature, register 
      address 19:
      Same as 19

21, Period 5_room temperature, Period 6_room temperature, register 
      address 20:
      Same as 19

22, Period 7_room temperature, Period 8_room temperature, register 
      address 21:
      Same as 19

IX. Installation Instruction

This product is suitable for standard 80*80mm wall box and 60 mm 
european round box.

1.Connect the line of power and valve into the terminals. Fix the wall plate 
into the wall box by a screwdrive.

2.Connect the lines with the LCD board.

3.Connect the LCD board into the wall plate.

NOTICE:

 The installation wire should be 1.5-2.5mm2.