171 425 61 14-01
List of components
A1 Oil burner control
A2 Twin thermostat
F1 Fuse, max. 10A
H1 Alarm lamp
H2 Signal lamp (optional)
M1 Burner motor
P1 Time meter (optional)
R1 Photoresistor
S3 Main switch
T1 Ignition transformer
Y1 Solenoid valve
Mains connection and fuses in
accordance with local regulations.
Oil burner control: LOA21... / LOA24.../ LMO14.../ LMO24...
Wiring diagram
ELECTRIC EQUIPMENT
1(2)
LMO14.113...
LMO24.255...
LOA24.171...
Pre-ignition time:
15 s
25 s
13 s
Pre-purge time:
16 s
26 s
13 s
Post-ignition time:
3 s
5 s
15 s
Safety lock-out time:
< 10 s
< 5 s
< 10 s
Reset time after lockout:
< 1 s
< 1 s
< 50 s
Reaction time on lame failure:
< 1 s
< 1 s
< 1 s
Ambient temperature:
-5 +60°C
-20 - +60°C
-20 - +60°C
Min. current with lame established:
45 µA
45 µA
65 µA
Max. photo current at start:
5,5 µA
5,5 µA
5 µA
Enclosure:
IP 40
IP 40
IP 40
Control of photo current
Current through photo unit is measured with a d.c. ammeter (a moving coil
instrument connected in series with the photo unit).