96
Bentone
!
When the Purging in the lockout position function is used, the fan may only be
powered via a contactor and must not be connected directly to LMV37.4 (X3-05
pin 1)!
15.4.1.6 Prepurging
222 Gas: Prepurging
Index 0 = deactivated
Index 1 = activated
Factory settings marked with bald text
When using valve proving and 2 fuel valves of class A, prepurging is not
required (conforming to EN 676).
If not activated, it is nevertheless performed if one or several of the following
conditions apply:
• Alterable lockout position
• After an off time of >24 hours
• In the event of a power failure (power-on)
• In the event of shutdown due to an interruption of gas supply (safety
shutdown)
15.4.1.7 Prepurging time
225 Gas: Prepurging time
20 s
– 60 min
15.4.1.8 Postpurge time
234 Gas: Postpurge time (no external light test)
0,2 s
– 108 min
15.4.1.9 Postpurging in lockout position
190 Postpurging in lockout position
0 = deactivate (no-load position)
1 = active (postpurge position)
Factory settings marked with bald text.
When active, the Alarm in the event of start prevention function (parameter
210) is only possible to a limited extent!
The LMV37.4 system simply moves the actuators to the postpurge position.
A fan release contact cannot be controlled, as the alarm relay of the
LMV37.4 system cuts off the power supply to the outputs. With the Alarm in
the event of start prevention function, an external circuit that may be present
for controlling the fan release contact for purging in the lockout position is
activated via start prevention in standby mode.
Содержание BG 550i M
Страница 31: ...32 Bentone I I J G G G H 172 615 56 2018 08 10 ...
Страница 63: ...63 Bentone 13 2 Wiring diagram 172 615 84 1 2021 05 19 2 ...
Страница 64: ...64 Bentone 13 3 Wiring diagram RWF 50 3 172 615 84 1 2021 05 19 3 ...
Страница 65: ...65 Bentone 13 4 Wiring diagram RWF 50 2 172 615 84 1 2021 05 19 4 ...
Страница 66: ...66 Bentone 13 5 Wiring diagram Jumo 316 172 615 84 1 2021 05 19 5 ...
Страница 145: ......
Страница 146: ......
Страница 147: ......
Страница 148: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com ...