4. Settings
4.1
Example of basic setting
BF 1 KS 76-24
Burner output:
59 kW
Estimated nozzle output:
59 / 11.86*
=
4.97 kg/h
(*
Calorfic value Fuel oil
=
11.86 kWh/kg)
This provides the following nozzle according to the nozzle table, (see Technical
data).
Nozzle:
1.35 Gph
Pump pressure:
10.0 bar
Setting values for 59 kW according to basic setting diagram, (see Technical
data).
Air setting:
=
20.0
Insert setting:
=
14.0
BF 1 KSV 76-24
Burner output:
59 kW
Output increase, for burners with
preheater:
59 x 1.06
=
62.5 kW
Estimated nozzle output:
62.5 / 11.86*
=
5.27 kg/h
(*
Calorfic value Fuel oil
=
11.86 kWh/kg)
This provides the following nozzle according to the nozzle table, (see Technical
data).
Nozzle:
1.35 Gph
Pump pressure:
11.0 bar
Setting values for 59 kW according to basic setting diagram, (see Technical
data).
Air setting:
=
20.0
Insert setting:
=
14.0