18
Bentone
!
When servicing/replacing components that affect combustion, an analysis and soot test must
be carried out on the installation
.
5.4 Replacing the oil pump
1.
Switch off mains power, remove the cover and disconnect the
Europlug from the burner.
2.
Remove the oil hoses from the pump.
3.
Remove the burner from the boiler by loosening the screw (A)
4.
Loosen the hex nut from the stud bolt. Pull the electrical package
backwards and rotate approx. 90° clockwise. (G)
5.
Disconnect the solenoid valve cable from the pump.
6.
Disconnect the connection tube (D) from the pump.
7.
Loosen the screws (E), pull out the oil pump and remove the pump
coupling.
8.
Move the pump coupling (or replace) to the new oil pump and install
the pump in the burner. Tighten the screws and fi t the connection tube
(D).
9.
Connect the solenoid valve cable.
10. Refi t the electrical package.
11. Insert the burner into the boiler.
12. Fit the oil hoses (for conversion between single-pipe and double-pipe
systems, see Pump instructions).
13. Connect the Europlug and turn on the mains power.
14. Turn on the burner, air the pump, adjust the pressure, and check the
combustion.
D
E
E
G
Содержание B 1 FUV 63-16
Страница 31: ...171 905 28 ...
Страница 34: ......
Страница 35: ......
Страница 36: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com ...