System Monitor
80175-01
16
PROTOCOL SPECIFICATIONS
Example 2:
Read monitor status from a 6-channel temperature monitor in slot 7. The rack also
has a 6-channel temperature monitor in slot 1, with slots 3, 4, 5 and 6 empty.
Starting address (point number) = 3(5) = 15. Note that slot 2 is not considered an
empty slot because it is occupied by the double wide 6-channel monitor. The Read
Input Status command should request 3 status points starting at point number 15.
Point number 15 contains the slot 7 monitor's Alert status, point number 16 the
Danger status and point number 17 the not OK status. These status bits will be
packed into the three least significant bits of a single response byte.
43