M O N I T O R F U N C T I O N S
I
SYSTEM POWER-UP INHIBIT
The System Monitor provides a Power-up Inhibit function that allows each monitor to inhibit its
alarms during power-up, or whenever a system supply voltage falls below its operating level. After
power-up, the inhibit function remains active for approximately 2 seconds. The inhibit function can
also be activated by contact closure through terminals on the Power Input Module at the rear of
the rack.
SUPPLY VOLTAGES OK
Seven LEDs located behind the front panel of the System Monitor are ON to indicate when supply
voltages are functioning. The supply voltages are +VRH, +VRL, +7.5V, + 5 V REF, -7.5V, and -
VT. A green LED on the front panel (SUPPLIES OK), when ON, indicates that all supply voltages
are functional.
SYSTEM RESET
The System Monitor provides System Reset capability that is activated by either external contact
closure through terminals on the Power Input Module, or by pressing the RESET switch on the
front panel.
TRIP MULTIPLY
The System Monitor provides a trip multiply control that is activated by contact closure through
terminals on the Power Input Module. When activated, trip multiply allows the alarm setpoints to
be multiplied by a factor preset on monitors with Trip Multiply options installed. The Trip Multiply
function is indicated by a red LED on the front panel.
STATIC DATA BUS BUFFER
The System Monitor multiplexes signals from the Communications Processor to select static data
from the monitors. Static data signals from the monitor are buffered before being sent to the
Communications Processor. If the Serial Interface option is installed, the position and data select
signals from the Communications Processor are intercepted in the interface. If no Communications
Processor is connected the Serial Interface takes over control o f the position select and data
select signals to gather data.
OK RELAY
The System Monitor drives an OK Relay that is located on the Power Input Module. The single-
pole, double-throw (SPDT) relay is used to indicate that the 3300 rack is in an OK condition. The
OK Relay is set normally energized. The OK Relay is deactivated either by the system power-up
inhibit signal (from System Monitor), or by a not OK signal from the monitors.
3
Содержание 3300/01 Series
Страница 2: ...3300 01 SYSTEM MONITOR OPERATION MANUAL BENTLY re NEVADA PART NO 80175 01 ...
Страница 5: ...System Monitor 80175 01 Blank Page iv ...
Страница 7: ...System Monitor 8 0 1 7 5 0 1 Blank Page vi ...
Страница 58: ... System Monitor 80175 01 18 SCHEMATICS AND DRAWINGS 51 ...
Страница 59: ... 5 Z 5 s 0 0 3 T4 E a 1 p L SERIALINTERFACE SCHEMATIC SHEET 1 OF 4 ...
Страница 62: ... T 7 1 0 1 0 z g i i IS P ig SERIAL INTERFACE SCHEMATIC SHEET 4 OF 4 ...
Страница 64: ... I I ...
Страница 67: ... SYSTEM MONITOR SCHEMATIC SHEET 3 OF 6 ...
Страница 73: ...t ...