MAIN (red)
As per the green MAIN POWER LED. This LED will go ON during Mains
power failure (the MAIN LED has memory).
LOW BATTERY
ON
: - indicates that the control panel batteries are low, and therefore, in the
event of blackout, will not be able to guarantee proper functioning of the con-
trol panel. Wait for several hours - if the LED remains ON call the installer for
service.
BATTERY FAULT
ON
: - indicates that the batteries are either disconnected or empty, or that the
Battery protection fuse has burnt (see FUSES LED). Therefore, in the event of
blackout the control panel will stop functioning.
GROUND
ON
: - indicates that the control panel is leaking to Ground. Call the Installer
for immediate service!
FUSES
ON
: - indicates that either the polarity invertion fuse, or the 24 V Output
fuse has burnt, in the latter case, the devices connected to the 24 V Output
will be unable to function (the display will indicate the fuse in question).
Call the Installer for immediate service!
LOGIC UNIT
ON
: - indicates that the control panel blocked. Call the installer for service!
ADDRESS
ON
: - indicates a missing Loop device. Call the installer for service!
SAME ADDRESS
ON
: - indicates the presence of more than one device of the same type at
the same address. Call the installer for service!
SILENCE
ON
: - indicates the the Silenceable Output Points have been forced into
standby status. Press the SILENCE button to restore the previous status.
Silenced Output Points will be released automatically if another alarm con-
dition occurs or, after the programmed NIGHT Mode SILENCE Time.
Z01
÷
Z16
ON
: - indicates that the corresponding zone is in ALARM status. In the event
of false alarm - press the SILENCE button to force the SILENCEABLE Out-
puts momentarily into standby status, or press the RESET button to deactivate
all the outputs definitively.
Blinking
: - (3 sec. ON - 1 sec. OFF) indicates that the corresponding zone
is in PREALARM status. The zone will go into ALARM status after the pro-
grammed Prealarm Time, or will activate the FIXED delay (if programmed).
In the event of false alarm - press the RESET button to stop the automatic
procedure.
Blinking
: - (1 sec. ON - 0,5 sec. OFF) indicates - the FIXED delay is running.
The Zone will go into ALARM status when the programmed delay ends. In the
event of false alarm press the RESET button to stop the automatic procedure,
or press ACK button to add the PAS delay to the FIXED delay.
Blinking
: - (1 sec. ON - 2 sec. OFF) indicates - the PAS delay has been ad-
ded to the FIXED delay already running. The Zone will go into ALARM status
when the total time of both delay ends. In the event of false alarm press the
RESET button to stop the automatic procedure.
+
Press the TEST key to check the LEDs are functioning properly.