Burner lights but locks out 
after 5 seconds 

 

Live and neutral inverted  
Poor earth 

 

Check electrical connections 

 

 

 

 

 

 

Faulty ionisation probe 

 

Check electrical connection on 
probe. 
 
Check probe for cracks or 
damage. 
 
Replace ionisation probe . 

 

 

 

 

 

 

Faulty ignition 

 

Check the gas type is suitable 
for the heater. 
 
Check the inlet gas pressure. 
 
Check the head pressure. 
 
Check the gas supply pipes 
have been properly purged of 
air . 

 

 

 

 

 

Explosive start up. 

 

Faulty ignition electrode 

Replace ignition electrode 

 

 

 

 

 

 

Incorrect electrode position 

 

Reposition electrode correctly 
over the burner bar. 
 

 

 

 

 

 

 

Faulty burner tube 

Replace the burner tube 

 

 

 

 

 

 

Faulty ignition transformer 

Replace ignition transformer 

 

 

 

 

 

 

Faulty ignition  

 

Check the gas type is suitable 
for the heater. 
 
Check the inlet gas pressure. 
 
Check the head pressure. 
 
Check the gas supply pipes 
have been properly purged of 
air . 

 

 

 

 

 

 

heat exchanger dirty 

Check / clean heat exchanger 

 

 

 

 

 

 

 

 

 

 

 

Burner shuts down then 

 

 

 

re lights automatically . 
 
No indication lights on

 

Pressure differential switch not 
operating correctly 

 

Check that air pipe to switch not 
damaged or blocked. 
Check that the flue and 
combustion air pipes are clear. 
 
Check that the thermal overload 
on the flue venter has not 
operated 

 

 

 

 

 

 

Faulty pressure differential 
switch  

 

Replace differential switch 

 

 

 

 

 

 

Room thermostat in warm air 
flow 

 

Check position of thermostat 

Содержание RS/UHA2 105

Страница 1: ...ed unit heaters 2 stage TECHNICAL INFORMATION ASSEMBLY INSTRUCTIONS USE AND MAINTENANCE RS UHA 2 BENSON HEATING LUDLOW ROAD KNIGHTON POWYS LD7 1LP MAY 2003 Benson Heating is a divison of Benson Climat...

Страница 2: ...uctions for the safe installation use and maintenance of the appliance s Where proprietary items are incorporated into Benson Heating products detailed information and instructions are also provided a...

Страница 3: ...R THE USER Operation Servicing Heater indication lights Receipt of product Transport Dimension FOR THE INSTALLER Location Wall bracket dimensions Gas connection Flue and combustion options Electrical...

Страница 4: ...cond stage gas valve 2 C Fan capacitor FAN 1 Axial fan 1 FAN 2 Axial fan 2 type 5 F1 F2 Line fuse 6 3 A LF Green working light LL High temperature indication light LB Lockout indication RST Lockout re...

Страница 5: ...II Second stage gas valve 2 C Fan capacitor FAN 1 Axial fan 1 FAN 2 Axial fan 2 FAN 3 Axial fan 3 Type 7 F1 F2 Line fuse LF Green working light LL High temperature indication light LB Lockout indicat...

Страница 6: ...indicating gas type 6 Ensure settings are correct as per the manual and data plate CHANGE INJECTORS To change injectors Unscrew the natural gas injectors and replace them with the correct size inject...

Страница 7: ...en the gas isolating cock switch on the electrical supply set the room thermostat to the desired temperature The heater is now ready for operation GAS VALVE Model SIT 843 two stage The heater must onl...

Страница 8: ...ponents are correct for the installation including storage tank pipes and pressure valves etc Ensure that the pressure regulators are sealed after carrying out the conversion GAS PRESSURE REGULATION T...

Страница 9: ...orrect pressure according to the data plate is achieved Gas valve head pressure setting low fire Propane G31 When setting the gas pressure for propane low fire first stage contact SF should be open Th...

Страница 10: ...orking Check flue pipe and combustion air pipe are clear Faulty differential pressure switch Replace differential pressure switch Poor connection at pressure switch Check air pipe to switch is connect...

Страница 11: ...bar Faulty burner tube Replace the burner tube Faulty ignition transformer Replace ignition transformer Faulty ignition Check the gas type is suitable for the heater Check the inlet gas pressure Check...

Страница 12: ...correct and the air flow over the chamber is sufficient Faulty SND thermostat or control panel Replace SND thermostat or control panel Burner goes out due to the intervention of the TR thermostat and...

Страница 13: ...and the air flow over the chamber is sufficient Faulty thermostat Replace thermostat Faulty fan Check fan capacitor Check fan motor Intervention of thermal overload on fan Check electrical absorption...

Страница 14: ...heater Check the gas pressure Check burner head pressure The fan does not work Defective fan control Change fan control or SND thermostat Faulty fan Check fan capacitor Check the fan motor The heater...

Страница 15: ...B22 Single flue option with condensate tee and roof terminal combustion air from inside the room Type 1 2 3 4...

Страница 16: ...1000 with seal T Terminal with guard 100 U Condensate Tee with drain point V Pipe M M 100 L 200 without seal NOTE IMPORTANT MODEL 1 2 3 4 FLUE SPIGOT 100 female COMBUSTION AIR SPIGOT 100 female INSTA...

Страница 17: ...165 ITEM DESCRIPTION A Pipe M F 100 L 1000 with seal T Terminal with guard 100 U Condensate tee with drain point Z Pipe M F 100 L 250 with seal NOTE IMPORTANT MODEL 5 6 7 FLUE SPIGOT SIZE 100 male COM...

Страница 18: ...RIPTION A Flue pipe M F 100 L 1000 with seal H Bend 90 M F 100 with seal L Vertical co axial roof terminal kit 100 100 U Condensate tee with drain point V pipe M M 100 L 200 without seal NOTE IMPORTAN...

Страница 19: ...with seal N Vertical co axial roof terminal kit 100 150 P Adaptor F F 150 L 200 with seal Q Bend 45 M F 150 with seal R Pipe M F 150 L 140 with seal S Bend 90 F F 100 with seal U Condensate tee with d...

Отзывы: