138
7 - PARAMETER DESCRIPTION
Bits 4, 5, 6
of Seq Cntl
Description of Seq Count Function (Bits 4, 5, 6)
000
Time Base -
The current sequencer state will last for a time interval equal to the number “Seq
Count X” multiplied by the time base configured in the Seq Appl (APP 01) parameter.
Seq Appl Setting
Time to
Advance
Max Seq Time
1 sec Base
(1 sec) * (Seq Cnt X)
18.2 hours
0.1 sec Base
(0.1 sec) * (Seq Cnt X)
1.82 hours
0.01 sec Base
(0.01 sec) * (Seq Cnt X)
10.92 minutes
001
Pulse Count -
The current sequencer state will last until the number of pulses programmed into “Seq
Count X” is detected on terminal Vin1.
010
Low Analog Voltage Threshold -
The active sequencer state lasts until the voltage signal applied to
terminal Vin2 is < a value programmed into “Seq Count X”. The value programmed into “Seq Count
X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
NOTE:
The % of analog input after span and offset can be read in parameter I/O39(Vin2 Stat)
011
High Analog Voltage Threshold -
The active sequencer state lasts until the voltage signal applied to
terminal Vin2 is > a value programmed into “Seq Count X”. The value programmed into “Seq Count
X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
NOTE:
The % of analog input after span and offset can be read in parameter I/O39(Vin2 Stat)
100
Low Analog Current Threshold -
The active sequencer state lasts until the current signal applied to
Cin terminals is < a value programmed into “Seq Count X”. The value programmed into “Seq Count
X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
NOTE:
The % of analog input after span and offset can be read in parameter I/O39(Vin2 Stat)
101
High Analog Current Threshold -
The active sequencer state lasts until the current signal applied to
Cin Terminals is > a value programmed into “Seq Count X”. The value programmed into “Seq Count
X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
NOTE:
The % of analog input after span and offset can be read in parameter I/O39(Vin2 Stat)
110
Digital Comparison -
The active sequencer state lasts until the binary value of digital inputs
configured to Seq1, Seq2 and Seq3 is equal to the value programmed into “Seq Count X”.
NOTE:
“DIx Configure” parameters must be set to “Seq1, Seq2, and Seq3”.
Digital Input Terminals
Description
Seq 1
Seq 2
Seq 2
0
0
0
No Input active
1
0
0
Seq 1 active
0
1
0
Seq 2 active
1
1
0
Seq 1 & Seq 2 active
0
0
1
Seq 3 active
1
0
1
Seq 1 & Seq 3 active
0
1
1
Seq 2 & Seq 3 active
1
1
1
Seq 1, Seq 2, Seq 3 active
111
The sequencer will never advance if this option is selected
Содержание RSi S4 Series
Страница 4: ......
Страница 9: ...1 1 Introduction...
Страница 16: ...8 1 INTRODUCTION NOTES...
Страница 17: ...9 2 Technical Specifications...
Страница 28: ...20 2 TECHNICAL SPECIFICATIONS NOTES...
Страница 29: ...21 3 Installation...
Страница 37: ...29 4 Connections...
Страница 51: ...43 4 CONNECTIONS 4 5 2 S4 Wiring Diagram S4 Series Wiring Diagram...
Страница 56: ...48 4 CONNECTIONS NOTES...
Страница 57: ...49 5 Keypad Operation and Programming...
Страница 70: ...62 NOTES 5 KEYPAD OPERATION AND PROGRAMMING...
Страница 71: ...63 6 Parameter Groups...
Страница 82: ...74 NOTES 6 S4 Parameter Groups...
Страница 83: ...75 7 Parameter Descriptions...
Страница 149: ...141 8 Troubleshooting Maintenance...
Страница 159: ...151 9 Motor Characteristics...
Страница 162: ...154 9 MOTOR CHARACTERISTICS NOTES...
Страница 163: ...155 10 Options...
Страница 165: ...157 11 Appendices...