BENNING MA 4 measuring adapter
4
Pos.
Meaning
1
PE socket for PE test probe (for
R
PE
cable test)
2
CEE connector: 16 A, 50 Hz to 60 Hz, 380 V to 415 V
3L+N+PE, 6h
3
CEE connector: 16 A, 50 Hz to 60 Hz, 230 V
L+N+PE, 6h
4
CEE connector: 32 A, 50 Hz to 60 Hz, 380 V to 415 V
3L+N+PE, 6h
5
The mains LED lights up as soon as 230 V are connected to the shock-proof plug.
6
The LED indications L1-N, L2-N, L3-N light up as soon as the corresponding connections have been
established (e. g. via extension cables).
7
Rotary switch
Cable
The switch can be used to toggle between all three phases and the individual phases. This
function is active when the rotary function selector switch (pos. 8) is set to the cable test
function. The testing personnel can use this to detect or limit faults during the cable function
test. The switch is not used during the functional testing of devices.
8
Rotary switch
Function
This rotary selector switch can be used to toggle between cable test, appliance test, appli-
ance test 1 mA and appliance test +3 mA. The I
PE
currents of 1 mA and 3 mA are only gen-
erated when testing with mains voltage.
No fault current is generated in the switch position of cable testing!
9
CEE socket: 16 A, 50 Hz to 60 Hz, 380 V to 415 V
CEE socket: 16 A, (3L+N+PE, 6h)
10
CEE socket: 16 A, 50 Hz to 60 Hz, 230 V
CEE socket: 16 A, (L+N+PE, 6h)
11
CEE socket: 32 A, 50 Hz to 60 Hz, 380 V to 415 V
CEE socket: 32 A, (3L+N+PE, 6h)
12
Shock-proof plug to the tester
Shock-proof plug (types E and F)
13
Mains connection
CEE 32 A connector (3L+N+PE, 6h)
14
Mains fuse
T 16 A (6.3 x 32)
15
Mains connection for tester
Shock-proof socket (type E)